Johnson Controls WT-4002-MCR Installation Instructions Manual page 10

Wt-4000 series pneumatic-to-direct digital control (ddc) room thermostats
Table of Contents

Advertisement

Net Config Screen
1. While in the Configuration Mode, press the
Up/Down buttons to select the Net Config option
(Figure 6).
Mesh
Net Config
Fan Mode
Standalone
Maintenance
Figure 6: Selecting Net Config
2. Press
to confirm the selection.
3. Press the Up/Down buttons to select CH to change
the radio channel number, GI to change the device
network group ID, and DI to change the unique
thermostat device ID (Figure 7).
Note: The high byte of the device ID must be in the
range of 71 to 80. The low byte can be set to any value.
Network
Information
CH 11
GI
111.111
DI
Figure 7: Selecting CH, GI, or DI
4. Press
to confirm the selection. The LCD
returns to the normal operation screen, and the
settings are effective immediately.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions
71.40
Maintenance – Pneumatic Settings
1. While in the Configuration Mode, press the
Up/Down buttons to select the Maintenance option
(Figure 8).
Mesh
Net Config
Fan Mode
Standalone
Maintenance
Figure 8: Selecting Maintenance
2. Press
to confirm the selection.
3. Press the Up/Down buttons to select the
Dir Acting, SP Psi, Gain, Prop Bnd, or Unoc Psi
option (Figure 9).
Dir Acting
SP Psi
   
Gain
Prop Bnd
Unoc Psi
Figure 9: Selecting the Pneumatic Settings
4. Press
to edit the selected option, which is
highlighted on the menu.
5. Change the direction as desired (Figure 10).
Dir Acting
SP Psi
  
Gain
Prop Bnd
Unoc Psi
Figure 10: Changing the Direction
a. Press the Up button
acting (Dir Acting).
b. Press the Down button
acting (Rev Acting).
10
 
 
     
9.0
     
2.0
6.0
       
0.0
 
 
     
9.0
     
2.0
6.0
       
0.0
to enable direct
+
to enable reverse
-