Technical Specifications

TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers

Power Requirements
USB Port Power Rating
Relay Contact Rating
Binary Inputs
Analog Inputs
Temperature Sensor Type
Wire Size
MS/TP Network Guidelines
Temperature
Backlit Display
Range
Heating Control
Cooling Control
Accuracy
Temperature
Minimum Deadband
Occupancy Sensor Motion
Detection (Occupancy Sensing
Models)
Ambient
Operating
Conditions
Storage
Compliance
BACnet
International
United States
Canada
Europe
Australia and
New Zealand
Shipping
Models without
Weight
Occupancy
Sensor
Models with
Occupancy
Sensor
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these
specifications, consult the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or
misuse of its products.
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
19 to 30 VAC, 50/60 Hz, 4 VA at 24 VAC nominal, Class 2 or
safety extra-low voltage (SELV)
120 to 250 mA current draw supported
19 to 30 VAC, 1.0 A maximum, 15 mA minimum, 3.0 A in-rush, Class 2 or SELV
Voltage free contacts across terminal COM to terminals BI1 or BI2
Nickel, platinum, A99B, 2.25k ohm NTC, 10k ohm NTC, 10k ohm NTC Type 3
across terminal COM to terminals R SEN
Local 1k ohm platinum sensor
18 AWG (1.0 mm diameter) maximum, 22 AWG (0.6 mm diameter) recommended
Up to 100 devices maximum for each Network Automation Engine (NAE);
4,000 ft (1,219 m) maximum cable length. Refer to the MS/TP Technical Bulletin for
the Metasys, FX, or Verasys system installed.
-40.0°F/-40.0°C to 122.0°F/50.0°C in 0.5° increments
40.0°F/4.5°C to 90.0°F/32.0°C
54.0°F/12.0°C to 100.0°F/38.0°C
±0.9F°/±0.5C° at 70.0°F/21.0°C typical calibrated
2F°/1C° between heating and cooling
Minimum of 94 angular degrees up to a distance of 15 ft (4.6 m);
based on a clear line of sight
32 to 122°F (0 to 50°C); 95% RH maximum, noncondensing
-22 to 122°F (-30 to 50°C); 95% RH maximum, noncondensing
BACnet Testing Laboratories™ (BTL) 135-2001 Listed BACnet Application Specific
Controller (B-ASC)
UL Listed, File E27734, CCN XAPX, Under UL60730
FCC Compliant to CFR 47, Part 15, Subpart B, Class B
UL Listed, File E27734, CCN XAPX7, Under E60730
Industry Canada, ICES-003
CE Mark – Johnson Controls declares that this product is in compliance
with the essential requirements and other relevant provisions of the EMC Directive
and the RoHS Directive.
RCM Mark, Australia/NZ Emissions Compliant
0.75 lb (0.34 kg)
0.77 lb (0.35 kg)
41

Advertisement

Table of Contents
loading

This manual is also suitable for:

Tec3331 seriesTec3630 seriesTec3631 series

Table of Contents