Ms/Tp Bus Objects Tables; Tec26X6(H)-4 And Tec26X6H-4+Pir Series Thermostat Controllers - Johnson Controls TEC2645-4 Technical Bulletin

Network temperature and humidity controllers
Table of Contents

Advertisement

MS/TP Bus Objects Tables

TEC26x6(H)-4 and TEC26x6H-4+PIR Series Thermostat Controllers

Table 3: TEC26x6(H)-4 and TEC26x6H-4+PIR Series MS/TP Bus Objects
(Part 1 of 7)
Point Name
1, 2
Room Temp
3
Room Temp Override
3, 4
Outdoor Temperature
Room Humidity
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
Room Humidity Override
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
5
Supply Temperature
Dehumidification Lockout
(TEC2636-4, TEC2636H-4,
TEC2636H-4+PIR, TEC2656-4,
TEC2656H-4, and
TEC2656H-4+PIR Models)
3
AUX Command
Sequence of Operation
3
System Mode
TEC Series BACnet® MS/TP Network Temperature and Humidity Controllers Technical Bulletin
Thermostat Point
(Type/Address)
AV 7
BV 8
AV 9
AV 10
BV 11
AI 12
BV 13
BV 14
MSV 15
3
MSV 16
Range
-40.0°F/-40.0°C to
122.0°F/50.0°C
0 = Normal
1 = Override
-40.0°F/-40.0°C to
122.0°F/50.0°C
5 to 90% RH
0 = Normal
1 = Override
-40.0°F/-40.0°C to
122.0°F/50.0°C
0 = Disabled
1 = Enabled
0 = Off
1 = On
1 = Cooling Only
2 = Heating Only
3 = Cooling and Reheat
4 = Heating and Reheat
5 = Cool/Heat Four-Pipe
6 = Cool/Heat Four-Pipe and Reheat
1 = Off
2 = Auto
3 = Cool
4 = Heat
11