IMPORTANT: The WT-4000 Series
Pneumatic-to-DDC Room Thermostat is not
designed or intended for use in mission-critical or
life/safety applications.

North American Emissions Compliance

United States
Compliance Statement (Part 15.19)
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference,
and
2. This device must accept any interference
received, including interference that may cause
undesired operation.
Warning (Part 15.21)
Changes or modifications not expressly approved by
the party responsible for compliance could void the
user's authority to operate the equipment.
Canada
Industry Canada Statement
The term IC before the certification/registration
number only signifies that the Industry Canada
technical specifications were met.
Le terme « IC » précédant le numéro d'accréditation/
inscription signifie simplement que le produit est
conforme aux spécifications techniques d'Industry
Canada.
WT-4000 Series Pneumatic-to-Direct Digital Control (DDC) Room Thermostats Installation Instructions

Installation

The first step of the installation process is to plan the
layout of the devices on the building floor plan. This
process includes identifying the desired locations for all
WT-4000 Series Pneumatic-to-DDC Room
Thermostats, as well as the Johnson Controls
WT-BAC-IP Gateway.
Next, measure the radial distances between each
WT-4000 Series Room Thermostat and the
WT-BAC-IP Gateway, to determine if the distances are
within 200 ft (61 m). If the distance exceeds 200 ft
(61 m), Johnson Controls WT-ROUTER Routers must
be installed to relay signals between each room
thermostat and the associated gateway.
The ideal installation provides each room thermostat
with at least two routes of transmission to the gateway,
to ensure signal transmission success. The nominal
transmission range of each router in a standard
building is 200 ft (61 m). To ensure proper signal
transmission in a wireless mesh network, there should
be at least two routers, or one router and one gateway,
located within a 200 ft (61 m) radius of every room
thermostat.
In order for the devices to connect to the same mesh
network, they all must have the same group ID. Both
the group ID and the device ID can be changed in the
field; see Net Config Screen on page 10 for more
details.