Causes and corrective actions
Operation panel
E.OC3
indication
Name
Overcurrent trip during deceleration or stop
When the drive unit's output current reaches or exceeds approximately 200% of it's rated current or approximately
Description
250% of the rated motor current during deceleration (other than acceleration and constant-speed state), the
protective circuit is activated and the drive unit trips.
 Check for sudden speed reduction.
 Check for output short-circuit/ground fault.
 Check for too fast operation of the motor's mechanical brake.
Check point
 Check if the stall prevention operation level is set too high.
 Check that the drive unit capacity matches with the motor capacity.
 Check if a start command is given to the drive unit while the motor is coasting.
 Increase the deceleration time.
 Check the wiring to make sure that output short circuit/ground fault does not occur.
 Check the mechanical brake operation.
Corrective action
 Lower the setting of stall prevention operation level (refer to page 83).
 Choose drive unit and motor capacities that match.
 Input a start command after the motor stops.
Operation panel
E.OV1
indication
Name
Regenerative overvoltage trip during acceleration
If regenerative energy causes the drive unit's internal main circuit DC voltage to reach or exceed the specified value,
Description
the protective circuit is activated and the drive unit trips. The circuit may also be activated by a surge voltage
produced in the power supply system.
 Check for too slow acceleration. (e.g. during downward acceleration in vertical lift load)
Check point
 Check that the setting of Pr. 22 Stall prevention operation level is not too small.
 Decrease the acceleration time.
Corrective action
 Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886). (Refer to page 228.)
 Set the Pr. 22 Stall prevention operation level correctly.
Operation panel
E.OV2
indication
Name
Regenerative overvoltage trip during constant speed
If regenerative energy causes the drive unit's internal main circuit DC voltage to reach or exceed the specified value,
Description
the protective circuit is activated to stop the drive unit output. The circuit may also be activated by a surge voltage
produced in the power supply system.
 Check for sudden load change.
Check point
 Check that the setting of Pr. 22 Stall prevention operation level is not too small.
 Keep load stable.
 Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886). (Refer to page 228.)
Corrective action
 Use the brake resistor, brake unit or power regeneration common converter (FR-CV) as required.
 Set the Pr. 22 Stall prevention operation level correctly.
Operation panel
E.OV3
indication
Name
Regenerative overvoltage trip during deceleration or stop
If regenerative energy causes the drive unit's internal main circuit DC voltage to reach or exceed the specified value,
Description
the protective circuit is activated to stop the drive unit output. The circuit may also be activated by a surge voltage
produced in the power supply system.
Check point
Check for sudden speed reduction.
 Increase the deceleration time. (Set the deceleration time which matches the moment of inertia of the load)
 Make the brake cycle longer.
Corrective action
 Use regeneration avoidance function (Pr. 882, Pr. 883, Pr. 885, Pr. 886). (Refer to page 228.)
 Use the brake resistor, brake unit or power regeneration common converter (FR-CV) as required.
258
FR-PU07
OC During Dec
FR-PU07
OV During Acc
FR-PU07
Stedy Spd OV
FR-PU07
OV During Dec