Terminal Connection Diagram; Wiring - Mitsubishi Electric FR-D720-0.2K-G Instruction Manual

S-pm geared motor drive unit fr-d700-g series
Table of Contents

Advertisement

Wiring

2.1
Wiring
2.1.1

Terminal connection diagram

Sink logic
Main circuit terminal
Control circuit terminal
MCCB
Three-phase
AC power
supply
Control input signals (No voltage input allowed)
Forward
The function of these
rotation start
terminals can be
Reverse
changed to the reset
rotation start
signal, etc. with the input
terminal assignment
(Pr. 178 to Pr. 182).
Multi-speed selection
*2 When using terminals
PC-SD as a 24VDC
power supply, take care
not to short across
terminals PC and SD.
(Common for external power supply transistor)
Speed setting signals (Analog)
*3 Terminal input specifications
can be changed by analog
input specifications
switchover (Pr. 73).
Terminal 10 and terminal 2
are used as PTC input
terminal (Pr. 561).
*4 It is recommended to
use 2W1kΩ when the
speed setting signal is
changed frequently.
*5 Terminal input specifications can be changed by analog
input specifications switchover (Pr. 267). Set the
voltage/current input switch in the "V" position to select
voltage input (0 to 5V/0 to10V) and "I" (initial value) to
select current input (4 to 20mA).
To use terminal 4 (initial setting is current input), set "4"
in any of Pr. 178 to Pr. 182 (input terminal function
selection) to assign the function, and turn ON AU signal.
For manufacturer *9
NOTE
 To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
 After wiring, wire offcuts must not be left in the drive unit.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the drive unit clean. When drilling mounting
holes in an enclosure etc., take caution not to allow chips and other foreign matter to enter the drive unit.
14
*
1. DC reactor (FR-HEL)
When connecting a DC reactor, remove the
jumper across P1 and P/+
Earth
(Ground)
MC
R/L1
S/L2
T/L3
Earth
(Ground)
STF
STR
RH
High
speed
RM
Middle
speed
RL
Low
speed
SD
Contact input common
PC
24VDC power supply
10(+5V)
3
Speed
setting
2 0 to 5VDC
2
potentiometer
(0 to 10VDC)
1/2W1kΩ
*4
5(Analog common)
1
Terminal 4
(+)
4 4 to 20mADC
input
(Current
(-)
input)
V
Voltage/current
input switch
S1
S2
SC
Brake unit
(Option)
*1
R
*6
PR N/-
Jumper
P1
P/+
Inrush current
limit circuit
Main circuit
Control circuit
24V
*2
*3
PU
connector
0 to 5VDC
*5
0 to 10VDC
I
*5
*6 Brake resistor (FR-ABR, MRS type, MYS
type)
Install a thermal relay to prevent an
overheat and burnout of the brake resistor.
(The brake resistor cannot be connected
to the 0.2K.)
V
W
Relay output
C
Terminal functions vary
B
by Pr. 192 A,B,C terminal
Relay output
function selection
(Fault output)
A
Open collector output
Terminal functions vary by
RUN
Pr. 190 RUN terminal function
Running
selection
Open collector output common
SE
Sink/source common
Calibration resistor
+
-
FM
*7
SD
*7 It is not necessary when
calibrating the indicator
from the operation panel.
*8
*8 Operation and parameter setting can be
done from the parameter unit
(FR-PU07) and the enclosure surface
operation panel (FR-PA07).
(Use the option cable (FR-CB2
RS-485 communication can be utilized
from a personal computer and other
devices.
*9 The terminals S1, S2, SC, and SO are for
manufacturer setting. Do not remove the
shortening wires across the terminals S1
and SC and the terminals S2 and SC.
For manufacturer *9
SO
Motor
M
Earth (Ground)
Indicator
(Speed meter, etc.)
Moving-coil type
1mA full-scale
).)