REMARKS
 If a fault is already occurring in the drive unit, a fault cannot be initiated by Pr. 997.
 The retry function is invalid for the fault initiated by the fault initiation function.
 If another fault occurs after a fault has been initiated, the fault indication does not change.
The fault is not saved in the fault history either.

4.19.7 Batch setting Mitsubishi Electric HMI (GOT) connection parameters (Pr. 999)

 Communication parameters for the Mitsubishi Electric HMI (GOT) connection can be set as a batch.
Multiple parameters are changed automatically. Users do not have to consider each parameter number. (Parameter
setting mode)
Parameter
Name
Number
Automatic parameter
999
setting
 The read value is always "9999."
(1)
Automatic parameter setting
Setting Pr. 999 = "10" will automatically set the communication parameters required to connect a GOT to the PU
connector.
To operate in the parameter setting mode, go to "AUTO"
The following tables show which parameters are changed in each of the automatic parameter settings.
NOTE
 If the automatic setting is performed with Pr. 999 or the parameter setting mode, the listed settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the listed parameters will not cause any problem.
GOT initial setting (PU connector) (Pr. 999 = "10")
Parameter
Number
79
Operation mode selection
118
PU communication speed
119
PU communication stop bit length
120
PU communication parity check
121
Number of PU communication retries
122
PU communication check time interval
123
PU communication waiting time setting
124
PU communication CR/LF selection
340
Communication startup mode selection
549
Protocol selection
REMARKS
 Always perform a drive unit reset after the initial setting.
Initial Value
Setting Range
9999 
(Pr. 999)
"GOT", then write "1".
Initial
Name
Value
10
GOT initial setting (PU connector)
9999
No action
Automatically Set to
0
0
192
192
1
10
2
1
1
9999
0
9999
9999
0ms
1
1
0
1
0
0
Useful functions
Description
Refer to Page
164
184
184
184
184
184
184
184
176
203
239
4