Table 10: Menus and Submenus (Part 9 of 9)
Level 1
Level 2
(LCD Screen Name)
Commissioning
Supply Air Temperature
Heat Command
Cool Command
Supply Fan
Aux
Update
View Version
Load Firmware
Restore*
Backup*
1.
If the value is outside min/max limits, it is reassigned to the midpoint between min and max.

Troubleshooting

Table 11: Fault List (Part 1 of 3)
Faults
Remote Zone Temp Fail
Supply Temp Fail
Outdoor Temp Fail
Internal Sensor Fail
TEC3000 Series Single- or Two-Stage Economizer Thermostat Controllers Installation Instructions
Probable Causes
The External Zone Temperature sensor
has been disconnected or has failed.
The External Supply Temperature
sensor has been disconnected or has
failed.
The External Outdoor Air Temperature
sensor has been disconnected or has
failed.
An internal sensor has failed on the
TEC.
Level 3
Available Values
(Default Values)
Display Current
Temperature
0%
0 to 100%
0%
0 to 100%
No
Yes or No
No
Yes or No
x.x.x.xxxx
Current Release of Software
File list from USB drive
File list from USB drive or local storage
*Configuration can be backed up to the
USB drive and restored to similar models
to expedite the commissioning process.
File list from USB drive or local storage
*Configuration can be backed up to the
USB drive and restored to similar models
to expedite the commissioning process.
Solutions
1. Check the wiring of the sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
1. Check the wiring of the sensor.
2. If intentionally disconnected, result fault by
entering the menu, enter Control Setup, and
select Inputs to reset the sensors.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
1. Check the wiring of sensor.
2. If intentionally disconnected, reset sensors
through the menu.
3. If the problem persists, order replacement
units and return the affected devices to
Johnson Controls under the RMA program.
Order replacement units and return the affected
devices to Johnson Controls under the RMA
program.