Description of parameters
 Using Pr. 65, you can select the fault that will cause a retry. No retry will be made for the fault not indicated. (Refer to page
126 for the fault description. )
 indicates the faults selected for retry.
Fault for
Retry
0
E.OC2
E.OV2
E.THT
E.IPF
E.UVT
E.OHT
E.OP3
E.CDO
E.ILF
E.8
NOTE
 The data stored as the error reset for retry is only that of the fault which occurred the first time.
 When an converter fault is reset by the retry function at the retry time, the accumulated data of the electronic thermal
relay function, etc. are not cleared. (Different from the power-ON reset.)
Stay away from the motor and machine when the converter trips while the retry function is selected. Motor and
machine will start suddenly (after the reset time has elapsed) after a converter trip.
If the retry function has been selected, apply the CAUTION stickers, which are supplied with the Instruction
Manual of the inverter, to easily visible places.

3.4.18 Reset selection/disconnected PU detection/PU stop selection (Pr. 75)

You can select the reset input acceptance, disconnected PU (FR-DU07-CNV/FR-PU07) connector detection function
and PU stop function.
Parameter
Number
Reset selection/disconnected PU
75
detection/PU stop selection
The Pr. 75 value can be set any time. Also, if parameter (all) clear is performed, this setting will not return to the initial value.
Pr. 75
Setting
0
Reset input always enabled
Reset input is enabled only when a fault
1
occurs.
2
Reset input always enabled
Reset input is enabled only when a fault
3
occurs.
14
Reset input always enabled
(Initial setting)
Reset input is enabled only when a fault
15
occurs.
16
Reset input always enabled
Reset input is enabled only when a fault
17
occurs.
92
Pr. 65 Setting
1
2
3
4
Name
Initial Value
Reset Selection
CAUTION
Setting Range
14
0 to 3, 14 to 17
Disconnected PU detection
If the PU is disconnected, operation will
be continued.
When the PU is disconnected, the
converter trips.
If the PU is disconnected, operation will
be continued.
When the PU is disconnected, the
converter trips.
Description
For the initial setting, reset is always
enabled, without disconnected PU
detection, and with PU stop function are
set.
PU Stop Selection
Stop by
is not available.
Press
to stop.