Wiring of control circuit

2.13 Wiring of control circuit

2.13.1 Description of control circuit terminal

indicates that terminal functions can be selected using Pr. 3 to Pr. 7 (input terminal function selection) and Pr. 11 to Pr. 16
(output terminal function selection)(Refer to page 76, 78)
(1) Input signal
Terminal
Type
Terminal Name
Symbol
RES
Reset
SOF
Converter stop
Inrush current limit
ROH
resistor overheat
protection
X1
Monitor switching
X2
Contact input
common
(sink) (initial setting)
External transistor
SD
common (source)
24VDC power supply
common
External transistor
common
(sink) (initial setting)
PC
Contact input
common (source)
24VDC power supply
58
Description
Used to reset fault output provided when a fault occurs.
Turn ON the RES signal for more than 0.1s, then turn it OFF.
Turning ON the SOF signal stops the converter.
RDY signal turns OFF, limit MC turns ON
200V class
Connect this terminal to terminal ROH1 of the
7.5K to 75K
outside box (FR-HCB2). The ROH signal is
400V class
input to stop the converter operation when
7.5K to 220K
the limit resistor may overheat.
An auxiliary contact (NO contact) of a limit
resistor MC, a limit resistor (with thermostat)
(NC contact), and a filter capacitor alarm
400V class
detector (NC contact, 400K, 560K) are
280K to 560K
connected to stop the converter operation
when overheating of the limit resistor
becomes a concern and when a filter
capacitor is faulty.
FM and AM output or PU monitor display can be switched by a
combination of ON/OFF of X1 signal and X2 signal.
Common terminal for contact input terminal (sink logic) and terminal
FM.
When connecting the transistor output (open collector output), such
as a programmable controller in source logic, connect the external
power supply common for transistor output to this terminal to
prevent a malfunction caused by undesirable currents.
Common output terminal for 24VDC 0.1A power supply (terminal
PC).
Isolated from terminals 5, SE and SE2.
When connecting the transistor output (open collector output), such
as a programmable controller in sink logic, connect the external
power supply common for transistor output to this terminal to
prevent a malfunction caused by undesirable currents.
Common terminal for contact input terminal (source logic)
Can be used as 24VDC 0.1A power supply.
Rated Specifications
Input resistance : 4.7k
Voltage at opening: 21
to 27VDC
Contacts at short-
circuited: 4 to 6mADC
Power supply voltage
range 19.2 to 28.8VDC
Permissible load current
100mA