Inspection items
Reinstallation (FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H110K)
1)After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" faces up.
<Fan side face>
2)Reconnect the fan connectors.
FR-HC2-H7.5K, H15K
FR-HC2-15K
3)Reinstall the fan cover.
1. Insert hooks into
2. Insert hooks until
holes.
FR-HC2-7.5K, 15K
FR-HC2-H7.5K, H15K
(Example for FR-HC2-7.5K)
NOTE
 Installing the fan in the opposite of air flow direction can cause the converter life to be shorter.
 Prevent the cable from being caught when installing a fan.
 Switch the power OFF before replacing fans. Since the converter circuits are charged with voltage even after power
OFF, replace fans only when the converter cover is on the converter to prevent an electric shock accident.
142
AIR FLOW
FR-HC2-7.5K
you hear a click
sound.
FR-HC2-30K or higher
FR-HC2-H30K to H110K
1. Insert hooks into
2. Insert hooks until
holes.
you hear a click
sound.
FR-HC2-30K or higher
FR-HC2-H30K to H110K
(Example for FR-HC2-55K)