Description of parameters
(3) CC-Link extended setting (Pr. 544)
The functions of the remote register can be extended. Refer to page 110 for the details of the remote I/O signals and the
remote registers.
Pr. 544 Setting
CC-Link Ver.
0 (Initial setting)
1
12


The program used for the conventional inverter series (FR-A5NC) can be used.
The upper 8 bits of RWw2 are not used for the link parameter extended setting.

When using the double setting of the CC-Link Ver.2, station data of the master station must be set to double.
(If the master station is CC-Link Ver.1, this setting is not available. )
REMARKS
 The setting becomes valid after converter reset. (Refer to page 124 for the converter reset.)
(4) I/O signal list
1)Remote I/O signals (32 points) (For details, refer to page 112.)
Device
No.
RYn0
Not used
RYn1
Not used
RYn2
Converter stop (terminal SOF function)
RYn3
Monitor switching (terminal X1 function)
RYn4
Monitor switching (terminal X2 function)
RYn5
Converter reset (terminal RES function)
ROH inrush resistance overheat detection
RYn6
(terminal ROH function)
RYn7
Not used
RYn8
Not used
RYn9
Not used
RYnA
Not used
RYnB
Not used
RYnC
Monitor command
RYnD
Not used
RYnE
Not used
RYnF
Instruction code execution request
RY(n+1)0 to
Reserved
RY(n+1)7
Not used
RY(n+1)8
(initial data process completion flag)
Not used
RY(n+1)9
(initial data process request flag)
RY(n+1)A
Error reset request flag
RY(n+1)B
to
Reserved
RY(n+1)F
("n" indicates a value determined by the station number setting. )

These signals are set in the initial setting. Using Pr. 3 to Pr. 7, input signals assigned to the device numbers can be changed.
For the available signals, refer to page 76.

These signals are set in the initial setting. Using Pr. 11 to Pr. 16, output signals assigned to the device numbers can be changed.
For the available signals, refer to page 78.

Output of the error status flag signal depends on the retry function setting.
110
Description
Occupies one station (FR-A5NC compatible)
1
Occupies one station
2
Occupies one station, double setting
Signal






Device No.
RXn0
Not used
RXn1
Not used
RXn2
Converter ready (inverter run enable signal)
RXn3
Converter reset(terminal RSO function)
RXn4
During converter run(terminal CVO function)
RXn5
Overload alarm(terminal Y1 function)
Power supply phase detection(terminal Y2
RXn6
function)

RXn7
Output voltage match (terminal Y3 function)
RXn8
Fault(terminal ABC function)
RXn9
Not used
RXnA
Not used
RXnB
Not used
RXnC
Monitoring
RXnD
Not used
RXnE
Not used
RXnF
Instruction code execution completion
RX(n+1)0 to
Reserved
RX(n+1)7
Not used
RX(n+1)8
(initial data process request flag)
Not used
RX(n+1)9
(initial data process completion flag)
RX(n+1)A
Error status flag
RX(n+1)B
Remote station ready
RX(n+1)C
to
Reserved
RX(n+1)F
Signal





