5 Troubleshooting
Event name
PLC System Processing Error
Meaning
A fatal error was detected in the PLC Function Module.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
None
Cause and
Assumed cause
correction
An error occurred in the software.
Attached
None
information
Precautions/
None
Remarks
* For details, refer to I/O Operation for Major Fault Level Controller Errors on page 5-7.
Event name
Real-Time Clock Stopped
Meaning
The oscillation of the real-time clock stopped. The real-time clock is set to an illegal time.
Source
PLC Function Module
Error attributes
Level
Effects
User program
System-defined
Variable
variables
_CurrentTime
Cause and
Assumed cause
correction
The battery voltage is low.
The battery connector has come
loose.
The Battery is missing.
Attached
None
information
Precautions/
This error is checked only when the power is turned ON. You can change the event level to the observation level. If you
Remarks
change the level to the observation level, recovery procedures are not required.
5 - 40
Source details
Major fault
Recovery
Stops.
Operation
Data type
---
Correction
Contact your OMRON representative.
Source details
Minor fault
Recovery
Continues.
Operation
Data type
DATE_AND_TIME
Correction
Replace the Battery. Then adjust the
real-time clock time.
Reconnect the connector and make
sure it is mated correctly. Then adjust
the real-time clock time.
Install a Battery. Then adjust the real-
time clock time.
Event code
40050000 hex
None
Detection
timing
Cycle the power
Log category
supply.
Stops.* A connection to the Sysmac Studio is not possible.
Name
---
Prevention
None
Event code
00070000 hex
None
Detection
timing
Error reset
Log category
The System Time is not defined. The clock information
recorded by CJ-series Units is also not defined.
Name
System Time
Prevention
Regularly replace the Battery.
Check for vibration and shock.
Install a Battery.
NX-series CPU Unit Hardware User's Manual (W535)
Continuously
System
At power ON or
Controller reset
System

Advertisement