Omron NX701-1700 User Manual page 144

Machine automation controller nx-series
Hide thumbs Also See for NX701-1700:
Table of Contents

Advertisement

5 Troubleshooting
Checking for Non-fatal Errors
Use the following methods to check for non-fatal errors.
Checking method
Checking the indicators
Checking with the trouble-
shooting function of Sysmac
Studio
Checking with the Trouble-
shooter of an HMI
Checking with instructions that
read function module error sta-
tus
Checking with system-defined
variables
*1 To perform troubleshooting from an HMI, connect the HMI to the built-in EtherNet/IP port on the CPU Unit.
Refer to the appendices of the NJ/NX-series Troubleshooting Manual (Cat. No. W503) for the applicable range
of the HMI Troubleshooter.
This section describes the above checking methods.
Checking the Indicators
 Checking the Level of a Controller Error
You can use the PWR indicator on the Power Supply Unit and the RUN and ERROR indicators on
the CPU Unit to determine the event level for an error. The following table shows the relationship
between the Controller's indicators and the event level.
PWR (green)
Lit
Lit
Lit
5 - 8
You can use the indicators to confirm the Controller error level, the error status
of the EtherCAT Master Function Module, and the error status of the Ether-
Net/IP Function Module.
You can check for current Controller errors, a log of past Controller errors, error
sources, error causes, and corrections.
You can check for current Controller errors, a log of past Controller errors, error
*1
sources, error causes, and corrections.
You can check the highest-level status and highest-level event code in the cur-
rent Controller errors.
You can check the current Controller error status for each function module.
Indicator
RUN (green)
Not lit
Lit
Lit
What you can check
ERROR (red)
Lit
Major fault level
Flashing (1-s intervals) Partial fault level
Minor fault level
Not lit
Observation
NX-series CPU Unit Hardware User's Manual (W535)
Event level

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx701-1600Nx-pd7001Nx701-1620Nx701-1720Nx-pa9001

Table of Contents