Omron NX701-1700 User Manual page 150

Machine automation controller nx-series
Hide thumbs Also See for NX701-1700:
Table of Contents

Advertisement

5 Troubleshooting
Event code
Event name
10010000 hex
Non-volatile
Memory
Restored or
Formatted
10020000 hex
Non-volatile
Memory Data
Corrupted
10080000 hex
Main Memory
Check Error
100A0000 hex
Data Not
Saved to Bat-
tery-backup
Memory
100B0000 hex
Non-volatile
Memory Data
Corrupted
100C 0000 hex Event Level
Setting Error
40020000 hex
PLC System
Processing
Error
40030000 hex
PLC System
Processing
Error
40040000 hex
PLC System
Processing
Error
40050000 hex
PLC System
Processing
Error
5 - 14
Meaning
Assumed cause
An error was
• The Controller power supply
detected in the non-
was turned OFF while the
volatile memory
BUSY indicator was lit.
check and file sys-
• The power supply to the Con-
tem recovery or for-
troller was interrupted momen-
matting was
tarily while the BUSY indicator
executed. Previous
was lit.
files may have been
deleted.
A file that must be
• The Controller power supply
in non-volatile
was turned OFF while the
memory is missing
BUSY indicator was lit.
or corrupted.
• The power supply to the Con-
troller was interrupted momen-
tarily while the BUSY indicator
was lit.
• The CPU Unit has failed.
An error was
• Conductive material has gotten
detected in the
inside.
memory check of
• Noise
the main memory in
• There is a software error.
the CPU Unit.
• The CPU Unit has failed.
An error occurred in
• An error occurred in the soft-
the software and
ware.
data could not be
saved in battery-
backup memory
during power-OFF
processing.
A file that must be
• The Controller power supply
in non-volatile
was turned OFF while the
memory is missing
BUSY indicator was lit.
or corrupted.
• The power supply to the Con-
troller was interrupted momen-
tarily while the BUSY indicator
was lit.
• The CPU Unit has failed.
The settings in the
• The event level settings are not
event level setting
correct because the power sup-
file are not correct.
ply to the Controller was inter-
rupted or communications with
the Sysmac Studio were dis-
connected during a download
of the event level settings.
• The event level settings are not
correct because the power sup-
ply to the Controller was inter-
rupted during a Clear All
Memory operation.
• Non-volatile memory failed.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
A fatal error was
• An error occurred in the soft-
detected in the PLC
ware.
Function Module.
Level
Maj
Prt
Min
Obs Info
S
S
S
S
S
S
S
S
S
S
NX-series CPU Unit Hardware User's Manual (W535)
Reference
page 5-33
page 5-34
page 5-35
page 5-36
page 5-37
page 5-38
page 5-39
page 5-39
page 5-39
page 5-40