5 Troubleshooting
Event code
Event name
102C 0000 hex Restore
Operation
Failed
5 - 24
Meaning
Assumed cause
• Password of Restore by sys-
tem-defined variable in the
Controller Setup does not
agree with the _Card1Resto-
reCmd.Password system-
defined variable.
• The DIP switch on the CPU
Unit is not set to allow starting
the restore of SD Memory Card
backups by specification with
system-defined variables.
• There is no such folder as
specified by the system-defined
variable.
• Required files are not set to
transfer in the setting of the
system-defined variable.
The restore opera-
• It was not possible to read the
tion ended in an
data to restore.
error.
• The SD Memory Card was
removed during a restore oper-
ation.
• Failed to restore Unit or slave.
• The SD Memory Card is dam-
aged.
Level
Maj
Prt
Min
Obs Info
S
NX-series CPU Unit Hardware User's Manual (W535)
Reference
page 5-67