Daikin CHYHBH05AA Installer's Reference Manual page 91

Hybrid for multi heat pump – heat pump module
Hide thumbs Also See for CHYHBH05AA:
Table of Contents

Advertisement

INFORMATION
▪ h=The height measured from the floor to the flare nut.
▪ H=The height measured from the floor to the bottom of
the casing.
▪ For intermediate H values (i.e., when H is between 2 H
values from the table), consider the value that
corresponds to the lower H value from the table. If
H=950  mm, consider the value that corresponds to
"H=900 mm".
▪ In cases where H≤600  mm, h is always considered to
be 600  mm, as specified in IEC  60335-2-40:2013 A1
2016, clause GG2.
▪ For intermediate A
between 2 A
values from the table), consider the
room
lower A
value from the table. If A
room
consider the value that corresponds to "A
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1A – 2017.10
values (i.e., when A
room
room
=12.5  m
room
2
=12 m
".
room
is
2
,
15 Technical data
Installer reference guide
91

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ehykomb33aChyhbh08aa

Table of Contents