To Perform A Test Run - Daikin CHYHBH05AA Installer's Reference Manual

Hybrid for multi heat pump – heat pump module
Hide thumbs Also See for CHYHBH05AA:
Table of Contents

Advertisement

INFORMATION
Start by performing a manual air purge. When almost all
the air is removed, perform an automatic air purge. If
necessary, repeat performing the automatic air purge until
you are sure that all air is removed from the system.
During air purge function, pump speed limitation [9‑0D] is
NOT applicable.
Air purge prerequisites
3
Install air purges on each part of the installation where the pipe
work goes down. (For example on a tank with connections on
top.)
4
Fill the circuit to ±2 bar.
5
Purge all radiators and all other air purges installed on the
circuit.
6
Repeat steps 2 and 3 until purging the radiators and the other
points does NOT longer lead to a pressure drop.
7
Make sure that the leaving water temperature home page, room
temperature home page, and domestic hot water home page
are turned OFF.
When an air bubble blocks the pump and there is no flow, a 7H error
can occur. In this case, stop the air purge function and restart the
operation. This will cause the bubble to leave the pump. Make sure
the pressure in the circuit is ±2 bar and refill if necessary.
To check if the air purge function is finished, monitor the flow rate. If
it stays constant when the pump is running at high or low speed, the
unit is properly purged. To monitor the flow rate, go to [6.1.8].
The air purge function automatically stops after 42 minutes.
To perform a manual air purge
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1 Set the user permission level to Installer. See
permission level to Installer" on
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Manual and press
4 Go to [A.7.3.4]
> Installer settings > Commissioning > Air
purge > Start air purge and press
function.
Result: The manual air purge starts and the following screen
appears.
Tue
Air purge
Flow rate
0.5
l/min
Speed
Low
Circuit
SHC
Bypass
Yes
Stop
Adjust
Scroll
5 Use the and buttons to scroll to Speed.
6 Use the
and
buttons to set the desired pump speed.
Result: Low
Result: High
7 If applicable, set the desired position of the 3-way valve (space
heating/domestic hot water). Use the and buttons to scroll to
Circuit.
8 Use the
and
buttons to set the desired position of the 3-way
valve.
Result: SHC or Tank
9 Set the desired position of the bypass valve. Use the
buttons to scroll to Bypass.
CHYHBH05+08AA + EHYKOMB33A
Daikin hybrid for multi heat pump – heat pump module
4P471761-1A – 2017.10
"To set the user
page 46.
> Installer settings >
.
to start the air purge
01:18
and
10 Use the
and
buttons to set the desired position of the
bypass valve.
Result: No (boiler not bypassed)
Result: Yes (boiler bypassed)
To perform an automatic air purge
Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1 Set the user permission level to Installer. See
permission level to Installer" on
2 Set the air purge mode: go to [A.7.3.1]
Commissioning > Air purge > Type.
3 Select Automatic and press
4 Go to [A.7.3.4]
> Installer settings > Commissioning > Air
purge > Start air purge and press
function.
Result: Air purging will start and the following screen will be
shown.
Tue
Air purge
Flow rate
0.5
l/min
Speed
Low
Circuit
SHC
Bypass
Yes
Stop
Adjust
Scroll
To interrupt air purge
1 Press
and press
to confirm the interruption of the air
purge function.
10.4.4

To perform a test run

Prerequisite: Make sure that the leaving water temperature home
page, room temperature home page, and domestic hot water home
page are turned OFF.
1 Set the user permission level to Installer. See
permission level to Installer" on
2 Go to [A.7.1]:
> Installer settings > Commissioning > Test
run.
3 Select a test and press
. Example: Heating.
4 Select OK and press
.
Result: The test run starts. It stops automatically when done
(±30 min). To stop it manually, press
INFORMATION
If 2 user interfaces are present, you can start a test run
from both user interfaces.
▪ The user interface used to start the test run displays a
status screen.
▪ The other user interface displays a "busy" screen. You
cannot use the user interface as long as the "busy"
screen is shown.
If the installation of the unit has been done correctly, the unit will
start up during test operation in the selected operation mode. During
the test mode, the correct operation of the unit can be checked by
monitoring leaving water temperature (heating mode) and tank
temperature (domestic hot water mode).
To monitor the temperature, go to [A.6] and select the information
you want to check.
10 Commissioning
"To set the user
page 46.
> Installer settings >
.
to start the air purge
01:18
"To set the user
page 46.
, select OK and press
.
Installer reference guide
71