Hybrid for multi heat pump – heat pump module
Hide thumbs Also See for CHYHBH05AA:
Table of Contents

Advertisement

6 Preparation
Special requirements for R32
Start
Input from installer:
▪ Total refrigerant charge (m
) (kg)
c
▪ Installation height (H) (m)
▪ Area of room A (A
) (m
)
2
room A
Use table 1 in chapter "Technical data" to
calculate the maximum refrigerant charge
(m
) (kg) allowed for room A.
max
m
≥m
?
max
c
Yes
The unit can be installed in room A at the
specified installation height, and without
further room size or ventilation requirements.
Unit can be installed at room A if:
▪ 2 ventilation openings (permanently open) are provided between room A and B, 1 at the top and 1 at the bottom.
▪ Bottom opening: The bottom opening must meet the minimum area requirements (VA
≥20 mm. The bottom of the opening must be situated ≤100 mm from the floor. At least 50% of the required opening area must be situated <200 mm from the
floor. The entire area of the opening must be situated <300 mm from the floor.
▪ Top opening: The area of the top opening must be larger than or equal to the bottom opening. The bottom of the top opening must be situated at least 1.5 m
above the top of the bottom opening.
▪ Ventilation openings to the outside are NOT considered suitable ventilation openings (the user can block them when it is cold). For ventilation opening
requirements, see "Ventilation opening requirements" in the chapter "Technical data".
Use the tables in
"15.4  Table 1 – Maximum refrigerant charge
allowed in a room: indoor unit"  on page 
Minimum floor area: indoor unit"  on page 
Minimum venting opening area for natural ventilation: indoor unit" on
page  93
to calculate the needed values to make sure that your
appliance is installed correctly.
Installer reference guide
16
Input from installer:
▪ Area of adjacent room B (A
Use table 2 in chapter "Technical data" to
calculate the total minimum floor area
(A
) (m
) required for the total refrigerant
2
min total
charge (m
) at the selected installation height
c
(H).
A
min total
No
Determine the refrigerant amount that exceeds
m
(dm) (kg). (dm=m
max
Use table 3 in chapter "Technical data" and
dm to calculate the minimum opening area for
natural ventilation between room A and
room B (VA
) (cm
min
correct outdoor unit.
90,
"15.5  Table 2 –
92,
"15.6  Table 3 –
CHYHBH
Room A: Room where CHYHBH is installed.
) (m
)
2
room B
Room B: Room adjacent to room A.
No
≤A
+A
?
room A
room B
Yes
–m
)
c
max
). Make sure to select the
2
). If the ventilation opening starts from the floor, the height must be
min
Daikin hybrid for multi heat pump – heat pump module
Room A
Room B
Contact your dealer.
CHYHBH05+08AA + EHYKOMB33A
4P471761-1A – 2017.10