Advertisement

rough framing - before appliance installation
EN
see-thru
1" [25mm]
minimum to
sides for vertical
venting.
When passing
through a
ceiling, use
firestop spacer
W500-0028 (not
supplied)
L
minimum
Ref
L
note:
Although the minimum enclosure height for the LVX series is 73", some venting
configurations that require more vertical rise will require a larger enclosure to pro-
vide minimum vertical clearance between vent pipes and combustibles.
30
W415-1710 / A / 07.27.17
GLASS GUARD
LVX38
LVX50
73" (185.4cm)
73" (185.4cm)
6" [152mm] minimum
0" to side standoffs
1/2" finishing flange
(4 sides)
0" to base of the
appliance
LVX62
LVX74
91" (231.1cm)
91" (231.1cm)
3" [76mm] to top
2" [51mm] to sides /
bottom
When passing through
a wall, use firestop
spacer assembly
W010-4178 (supplied)
0" to non-combustible
finishing such as brick
and stone. When using
non-combustible finish-
ing, only use firestop
spacer (W615-0162)
included in the firestop
assembly (W010-4178)