Field Setting; Indoor Unit; Indoor Fan Control During Thermostat Off In Cooling; Brightness Setting Of Multi-Coloured Lamp Of The Indoor Unit - Daikin 2MXM50M Service Manual

Ra r32 split & multi split m-series. ftxj-m series;ftxm-m series;ftxp-kv series;fdxm-f series;rxj-m series; rxm-m series;mxm-m series;mxm-n series
Table of Contents

Advertisement

ESIE16-02B
|
Part 5. Appendix

5.1. Field setting

5.1.1. Indoor unit

5.1.1.1. Indoor fan control during thermostat off in cooling

Model: FTXM-M, ATXM-M (BMS) / Remote controller: ARC466A33
Software logic change for thermostat OFF is for cooling operation (to increase SEER) (for main stream models FTXM/CTXM).
Temp
Model FTX25/35KM does not have remote controller which has such service mode.
Change fan on/off by remote controller (ARC480A11) in service mode.
1.
Normal operation on remote controller.
2.
Press "temperature (upper/lower) button" with "off button" in same timing (
3.
Press "temperature button" (
"SC
4.
Press "temperature button" (
1~10), select 4 and press "fan button" as decision (
5.
Press "temperature button" (
0~1), select 0 and press "fan button" as decision (0: fan ON, 1: fan OFF).

5.1.1.2. Brightness setting of multi-coloured lamp of the indoor unit

1.
Press TEMP and MODE buttons simultaneously.
2.
SC is displayed on the screen.
3.
Select L (light) with TEMP buttons up or down.
4.
Press MODE button to enter brightness setting mode.
5.
Press TEMP up or down to adjust brightness to L (low), H (high) or OFF.
6.
Press MODE button again for 5 seconds to exit.

5.1.1.3. ON/OFF button on the indoor unit

1.
Shortly press ON/OFF button indoor: auto, 25°C, auto fanspeed. To de-activate: shortly press ON/OFF again.
2.
Press ON/OFF button indoor 5-9 seconds: forced operation mode = forced cooling. To de-activate: press again for 10 seconds.
4/04/17
|
Version 1.1
RA R32 Split & multi split M-Series
Figure 5-1: How to change fan OFF to ON when in cooling thermo off
Mode
SC
during cooling thermo off
A
7
SU" rotation = segment 1), select SU and press "fan button" as decision (
Temp
Select
Mode
"SU"
Select "4"
Mode
0
1
0
FAN ON
during cooling thermo off
Mode
Select
go to "SC" service mode).
number is displayed at the lower right).
1
FAN OFF
Temp
AFTER 60 s
DISPLAY NORMAL
number is displayed at the lower left).
5.1. Field setting
Page 93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents