ESIE16-02B
|
Part 1. Introduction

1.3. General operation

These split units are used for comfort cooling and are equipped with an inverter.
The rotation speed rps (= rotation per second) of the inverter driven compressor, modulated by the inverter, can be varied
according the required capacity in the room.
The compressor capacity step is changed in order to reach target compression ratio. The target compression ratio is calculated
from deviation between actual and target condensation and evaporation temperature.
Tc (condensing temperature) is used in heating mode.
Te (evaporation temperature) is used if any indoor unit operates in cooling mode.
The evaporating temperature in the heat exchanger is controlled by the electronic expansion valve.
When indoor unit is selecting heating mode, discharge gas is supplied by the outdoor unit to the indoor unit.
When indoor unit is selecting cooling mode, liquid refrigerant is supplied by the outdoor unit to the indoor unit.
1. Compressor
2. Indoor heat exchanger
3. Expansion valve
4/04/17
|
Version 1.0
RA R32 Split & multi split M-Series
4. Outdoor heat exchanger
5. 4-way valve
6. Stop valves
1.3. General operation
Page 13