Daikin 2MXM50M Service Manual page 55

Ra r32 split & multi split m-series. ftxj-m series;ftxm-m series;ftxp-kv series;fdxm-f series;rxj-m series; rxm-m series;mxm-m series;mxm-n series
Table of Contents

Advertisement

ESIE16-02B
|
Part 2. Troubleshooting
5.
In case no voltage is measured across high pressure sensor connector: pin 1-3; do following checks:
I
NFORMATION
If 1 or more checks fail, replace the high pressure sensor.
Check 1
1.
Check main PCB (refer to
Check 2
1.
Check if the high pressure sensor connector is plugged into PCB.
Check 3
1.
Measure the voltage across high pressure sensor connector: pin 4-3; the measured voltage must be 5 VDC, if not replace
PCB.
4/04/17
|
Version 1.1
RA R32 Split & multi split M-Series
Outdoor unit PCB
+5V
GND
Measure DC voltage here
Microcomputer
A/D input
"Replacing main PCB" on page
S60
Red
4
Black
3
2
White
1
84).
2.4. Component checklist
Page 55