Part 3. Repair
Installation
C
AUTION
The oil in the compressor is hygroscopic. Remove the caps from the compressor piping as late as possible.
I
NFORMATION
Before installing a new compressor, determine the cause of the compressor failure and take all required corrective
actions.
I
NFORMATION
If the dampers are worn, replace the dampers. The bushings inside the dampers are recuperated for use with the new
dampers.
I
NFORMATION
Install the putty on the compressor.
Install the compressor sound insulation in the same location.
1.
Check damper status, replace when worn.
2.
First install the 3 (new) dampers (without the bushings) on the new compressor.
3.
Install the 3 bushings in the dampers.
4.
When installing the new compressor, remove the caps from the compression pipe and the suction pipe as late as possible.
5.
When soldering the compressor pipes, cover the compressor pipes with a wet cloth to prevent overheating the compressor
(and the oil in the compression pipe).
6.
Proceed in reverse order.