6.2.1
Liquid resin in storage vessel, level measurement
Note
Minimum distance from flange face to target is limited by Near Range (2.5.1.).
To obtain level measurement proportional to resin levels:
● Low Calibration Pt. = 5 m (16.4 ft) from sensor reference point
● High Calibration Pt.= 0.5 m (1.64 ft) from sensor reference point
● Max.fill/empty rate = 0.2 m/min (0.65 ft/min)
In the event of a loss of echo:
● SITRANS LR250 is to report a user-defined value of 4.5 m (14.76 ft) after 2 minutes.
①
②
③
④
Parameter type
Quick Start
Wizard
parameters
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
Sensor reference point
High calibration point
0.5 m
100% level
Parameter No. /Name
Material (1.2.)
Response Rate (1.3.)
Units (1.4.)
Operating mode (1.5.)
⑤
5 m
⑥
Low calibration point
⑦
0% level
Options/
Values
LIQUID
MED
M
LEVEL
Commissioning
6.2 Application examples
Function
Medium =1 m/minute
meters
Level
51