Liquid Resin In Storage Vessel, Level Measurement - Siemens SITRANS LR250 PROFIBUS PA Operating Instructions Manual

Radar
Table of Contents

Advertisement

6.2.1

Liquid resin in storage vessel, level measurement

Note
Minimum distance from flange face to target is limited by Near Range (2.5.1.).
To obtain level measurement proportional to resin levels:
● Low Calibration Pt. = 5 m (16.4 ft) from sensor reference point
● High Calibration Pt.= 0.5 m (1.64 ft) from sensor reference point
● Max.fill/empty rate = 0.2 m/min (0.65 ft/min)
In the event of a loss of echo:
● SITRANS LR250 is to report a user-defined value of 4.5 m (14.76 ft) after 2 minutes.
Parameter type
Quick Start
Wizard
parameters
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
Sensor reference point
High calibration point
0.5 m
100% level
Parameter No. /Name
Material (1.2.)
Response Rate (1.3.)
Units (1.4.)
Operating mode (1.5.)
5 m
Low calibration point
0% level
Options/
Values
LIQUID
MED
M
LEVEL
Commissioning
6.2 Application examples
Function
Medium =1 m/minute
meters
Level
51