6.1.3.7
Device address
Note
See Master Reset (Page 82) to reset Device Address to 126.
The unique address of the device on the network (also called PROFIBUS address).
Values
1. In PROGRAM mode, navigate to: Level Meter > (5.) Communication > (5.1.) Device Address.
2. Press RIGHT arrow
3. If required, key in a new value and press RIGHT arrow
new value.
4. Press Mode
SITRANS LR250 (PROFIBUS PA)
Operating Instructions, 01/2014, A5E32221386-AB
0 - 126. Default: 126
, RIGHT arrow
to return to Measurement mode.
6.1 Operating via the handheld programmer
, to open parameter view and enable Edit mode.
to accept it. The LCD displays the
Commissioning
49