Chapter 8 Optional Cards C2000 Series
Communication Parameters for VFD-C2000 Connected to Ethernet
When VFD-C2000 is link to Ethernet, please set up the communication parameters base on the table
below. Ethernet master will be able to read/write the frequency word and control word of VFD-C2000
after communication parameters setup.
Parameter
Source of frequency
P00-20
command setting
Source of operation
P00-21
command setting
Decoding method for
P09-30
communication
IP setting
P09-75
IP address -1
P09-76
IP address -2
P09-77
IP address -3
P09-78
IP address -4
P09-79
Netmask -1
P09-80
Netmask -2
P09-81
Netmask -3
P09-82
Netmask -4
P09-83
Default gateway -1
P09-84
Default gateway -2
P09-85
Default gateway -3
P09-86
Default gateway -4
P09-87
Disconnecting CMC- MOD01 from VFD-C2000
1.
Switch off the power supply of VFD-C2000.
2.
Remove the two screws (shown in Figure 6).
3.
Twist opens the card clip and inserts the slot type screwdriver to the hollow to prize the PCB off
the card clip (shown in Figure 7).
4.
Twist opens the other card clip to remove the PCB (shown in Figure 8).
Function
Set value (Dec)
[Figure 6]
[Figure 8]
8-16
The frequency command is controlled by
8
communication card.
The operation command is controlled by
5
communication card.
Decoding method for Delta AC motor
0
drive
0
Static IP(0) / Dynamic distribution IP(1)
192
IP address 192.168.1.5
168
IP address 192.168.1.5
1
IP address 192.168.1.5
5
IP address 192.168.1.5
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
255
Netmask 255.255.255.0
0
Netmask 255.255.255.0
192
Default gateway 192.168.1.1
168
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
1
Default gateway 192.168.1.1
Explanation
[Figure 7]