Specifications Of Control Terminal; Removable Terminal Block; Terminal Function; Factory Setting (Npn Mode) - Delta C2000 series User Manual

Classical field oriented control ac motor drive
Hide thumbs Also See for C2000 series:
Table of Contents

Advertisement

6-1 Specifications of Control Terminal

0-10V
0-10V
0-10V
AFM1
AFM2
AVI
-10-10V
0-20mA
0-20mA
AFM1
+10V AVI
ACI
MO1
MO2 MCM
AFM2
-10V AUI
ACM
S1
Wire Gauge: 26~16AWG(0.1281-1.318mm
Torque: (A) 5kg-cm [4.31Ib-in.] (0.49Nm) (As shown in figure above)
(B) 8kg-cm [6.94Ib-in.] (0.78Nm) (As shown in figure above)
Wiring precautions:
Reserves 5mm and properly install the wire into the terminal; fasten the installation by a
slotted screwdriver. If the wire is stripped, sort the wire before install into the terminal.
Flathead screwdriver: blade width 3.5mm, tip thickness 0.6mm
In the figure above, the factory setting for S1-SCM is short circuit. The factory setting for
+24V-COM is short circuit and SINK mode (NPN); please refer to Chapter 4 Wiring for more
detail.
Terminals

Terminal Function

Digital control signal common
+24V
(Source)
Digital control signal common
COM
(Sink)
FWD
Forward-Stop command
REV
Reverse-Stop command
MI1
~
Multi-function input 1~8
MI8
Digital frequency meter
DFM
DCM
Digital frequency signal common
Multi-function Output 1
MO1
(photocoupler)
0-20mA
Open
ACI
485
0-10V
120
+24V COM FWD
MI1
MI3
SCM DFM
DCM REV MI2
MI4

Removable Terminal Block

2
+24V5% 200mA
Common for multi-function input terminals
FWD-DCM:
ON forward running
OFF deceleration to stop
REV-DCM:
ON reverse running
OFF deceleration to stop
Refer to parameters 02-01~02-08 to program the
multi-function inputs MI1~MI8.
ON: the activation current is 6.5mA 11Vdc
OFF: leakage current tolerance is 10μA 11Vdc
Regard the pulse voltage as the output monitor signal
DFM
Duty-cycle: 50%
Min. load impedance: 1kΩ/100pf
DCM
Max. current: 30mA
Max. voltage: 30Vdc
The AC motor drive releases various monitor signals,
such as drive in operation, frequency attained and
overload indication, via transistor (open collector).
Chapter 6 Control TerminalsC2000 Series
RC2 RB2
RA2
B
MI5
MI7
SGND
MI6
MI8
SG+
SG-
),

Factory Setting (NPN mode)

6-3
A
RC1
RB1
RA1

Advertisement

Table of Contents
loading

Table of Contents