Boiler"/Group 2 - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Type b2ha, b2ka, 3.2 to 35 kw gas council no. -system boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 -combi boilers: 47-819-28; 47-819-29; 47-819-30
Table of Contents

Advertisement

Code 1

"Boiler"/group 2

Select "Boiler" for weather-compensa-
ted control units (see page 60).
Coding
Coding in the delivered condition
Single/multi boiler system
01:1
Do not adjust (only for
constant temperature
control units)
Burner service in 100 hours
21:0
No service interval (hours
run) selected
Service interval in months
23:0
No interval for burner
service
Service status
24:0
"Service" not shown on
display
Filling/Venting
2F:0
Venting program/fill pro-
gram disabled
"DHW"/group 3
Select "DHW" for weather-compensa-
ted control units (see page 60).
64
Select "2" for constant temperature con-
trol units (see page 60).
Possible change
21:1
The number of hours run
to
before the burner should
21:100
be serviced is adjustable
from 100 to 10 000 h
One step ≙ 100 h
23:1
Interval adjustable from 1
to
to 24 months
23:24
24:1
"Service" is shown on dis-
play (the address is auto-
matically set and must be
manually reset after a serv-
ice has been carried out)
2F:1
Venting program enabled
2F:2
Fill program enabled
Select "3" for constant temperature con-
trol units (see page 60).