Commissioning, inspection, maintenance
Further details regarding the individual steps
Function/system components
Operation with LPG
System only with two heating circuits with mixer with
extension kit for mixer (without unregulated heating
circuit)
■ with DHW cylinder or instantaneous water heater
■ without DHW cylinder or instantaneous water heat-
er
System without DHW circulation pump:
Heating circuit pump A1 connection at internal exten-
sion H1 or H2
System with DHW circulation pump:
Heating circuit pump A1 connection at extension
AM1, terminal A1
DHW circulation pump connection at extension AM1,
terminal A2
System with low loss header
Adjusting the heating curves (only for weather-compensated
control units)
The heating curves illustrate the relation-
ship between the outside temperature
and the boiler water or flow tempera-
ture.
To put it simply, the lower the outside
temperature, the higher the boiler water
or flow temperature.
The boiler water or flow temperature in
turn affects the room temperature.
Settings in the delivered condition:
■ Slope = 1.4
■ Level = 0
54
(cont.)
Adjust
Note
If the heating system includes heating
circuits with mixers, then the flow tem-
perature of the heating circuit without
mixer is higher by a selected differential
(8 K in the delivered condition) than the
flow temperature of the heating circuits
with mixers.
The differential temperature is adjusta-
ble via coding address "9F" in the "Gen-
eral" group.
Code
Group
82:1
"General"
00:8
"General"
00:7
"General"
53:2
"General"
04:0
"Boiler"