Boiler/Group "2 - Viessmann Vitocrossal 100 Series Service Instructions For Contractors

Gas condensing boiler with matrix cylinder burner, open flue and room sealed operation 80 to 318 kw/240 to 636 kw
Table of Contents

Advertisement

General/Group "1"
(cont.)
Coding in the delivered condition
Lock out controls
8F:0
Operation enabled in standard
menu and extended menu.
Note
The relevant code is only enabled
when you exit the service menu.
Set flow temperature for external demand
9B:70
Set flow temperature for external
demand 70 °C

Boiler/Group "2"

For weather-compensated control units, select
"Boiler" (see page 33).
Coding
Coding in the delivered condition
Single/multi-boiler system
01:1
Single boiler system (only for con-
stant temperature control units)
Boiler number
07:1
Boiler number in multi boiler sys-
tems (only for constant tempera-
ture control units)
Burner service in 100 hours
21:0
No service interval set (in hours
run)
Service interval in months
23:0
No time set for burner service in-
terval
Service status
24:0
"Service" not shown on the dis-
play
Filling/venting
2F:0
Venting program/filling program in-
active
Possible change
8F:1
Operation is blocked in standard
menu and extended menu. Emis-
sions test mode can be activated.
8F:2
Operation is enabled in standard
menu, but blocked in extended
menu. Emissions test mode can be
activated.
9B:0
Set flow temperature for external de-
to
mand adjustable from 0 to 127 °C
9B:127
(limited by boiler-specific parame-
ters)
For constant temperature control units, select Group
"2" (see page 33).
Possible change
01:2
Multi boiler system with Vitotronic
300-K
07:2
Boiler number 2 to 4 in multi boiler
to
systems
07:4
21:1
The number of hours run before the
to
burner should be serviced is adjust-
21:100
able from 100 to 10,000 h
One step
23:1
Interval adjustable from 1 to
to
24 months
23:24
24:1
"Service" shown on the display.
The address is set automatically and
must be reset manually after a serv-
ice.
2F:1
Venting program active
2F:2
Filling program active
Code 1
100 h
35