Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
A7
b0
X
b1
X
b5
X
b7
X
b8
X
bA
bb
116
Weath.-
System char-
comp.
acteristics
X
Control mode
as per deliv-
ered condition
X
Burner blocked Short circuit,
X
Control mode
as per deliv-
ered condition
X
Control mode
as per deliv-
ered condition
X
Burner blocked Boiler coding
X
Burner blocked Lead break,
X
Mixer regulates
to 20 °C flow
temperature.
X
Mixer regulates
to 20 °C flow
temperature.
Cause
Measures
Programming
Replace program-
unit faulty
ming unit
Check flue gas
flue gas tem-
temperature sen-
perature sen-
sor
sor
Communica-
Check connections
tion fault, pro-
and replace pro-
gramming
gramming unit if re-
unit
quired
Internal fault
Replace the control
unit
Plug in boiler cod-
card faulty
ing card or replace
if faulty
Check flue gas
flue gas tem-
temperature sen-
perature sen-
sor
sor
Communica-
Check extension
tion error, ex-
kit connections and
tension kit for
code.
heating circuit 2
(with mixer)
Communica-
Check extension
tion error, ex-
kit connections and
tension kit for
code.
heating circuit 3
(with mixer)