Fault Codes - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Type b2ha, b2ka, 3.2 to 35 kw gas council no. -system boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 -combi boilers: 47-819-28; 47-819-29; 47-819-30
Table of Contents

Advertisement

Troubleshooting

Fault codes

Dis-
Const.
played
fault
code
10
X
18
X
19
X
20
X
112
Weath.-
System char-
comp.
acteristics
X
Controls as if
the outside
temperature
were 0 °C
X
Controls as if
the outside
temperature
were 0 °C
X
Controls as if
the outside
temperature
were 0 °C
X
Regulates with-
out flow tem-
perature sen-
sor (low loss
header)
Cause
Measures
Short circuit,
Check outside tem-
outside tem-
perature sensor
perature sen-
(see page 129)
sor
Lead break,
Check outside tem-
outside tem-
perature sensor
perature sen-
(see page 129)
sor
Communica-
Check wireless
tion interrup-
connection (place
tion with wire-
wireless outside
less outside
temperature sen-
temperature
sor close to the
sensor
wireless base sta-
tion).
Log off outside
temperature sen-
sor then log on
again.
Replace wireless
outside tempera-
ture sensor.
Short circuit,
Check low loss
flow tempera-
header sensor (see
ture sensor
page 130)
Wireless
base sta-
tion installa-
tion and
service in-
structions