Commissioning/Service Reports - Viessmann VITODENS 200-W Installation And Service Instructions Manual

Type b2ha, b2ka, 3.2 to 35 kw gas council no. -system boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 -combi boilers: 47-819-28; 47-819-29; 47-819-30
Table of Contents

Advertisement

Commissioning/service reports

Settings and actual values
Static pressure
Supply pressure (flow pres-
sure)
= for natural gas E
= for natural gas LL
= for LPG
Tick gas type
Carbon dioxide content
CO
2
For natural gas
■ At lower heating output
■ At upper heating output
For LPG
■ At lower heating output
■ At upper heating output
Oxygen content O
2
■ At lower heating output
■ At upper heating output
Carbon monoxide content
CO
■ At lower heating output
■ At upper heating output
Set value Commis-
Date
Signature
mbar
≤ 57.5
kPa
≤ 5.75
mbar
17.4-25
kPa
1.74-2.5
mbar
17.4-25
kPa
1.74-2.5
mbar
42.5-57.5
kPa
4.25-5.75
% by vol.
7.5-9.5
% by vol.
7.5-9.5
% by vol.
8.8-11.1
% by vol.
8.8-11.1
% by vol.
4.0-7.6
% by vol.
4.0-7.6
ppm
< 1000
ppm
< 1000
Commissioning/service reports
Mainte-
sioning
nance/
Service
179