Viessmann VITODENS 200-W Installation And Service Instructions Manual page 124

Type b2ha, b2ka, 3.2 to 35 kw gas council no. -system boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 -combi boilers: 47-819-28; 47-819-29; 47-819-30
Table of Contents

Advertisement

Troubleshooting
Fault codes
(cont.)
Dis-
Const.
played
fault
code
EA
X
Eb
X
EC
X
124
Weath.-
System char-
comp.
acteristics
X
Burner in a fault
state
X
Burner in a fault
state
X
Burner in a fault
state
Cause
Measures
Ionisation
Check flue system;
current out-
remedy flue gas re-
side permissi-
circulation if re-
ble range dur-
quired.
ing calibration
In open flue opera-
(deviation
tion, prevent high
from previous
incidence of dust in
level too
the combustion
great)
air.
Press reset button
R.
Following several
unsuccessful reset
attempts, replace
boiler coding card
and press reset
button R.
Repeated
Check gap be-
flame loss
tween ionisation
during cali-
electrode and
bration
burner gauze as-
sembly (see
page 42).
Check allocation of
gas type (see
page 35).
Check flue system;
remedy flue gas re-
circulation if re-
quired.
Press reset button
R.
Parameter
Press reset button
fault during
R
calibration
or
Replace boiler cod-
ing card and press
reset button R.