Viessmann VITODENS 200-W Installation And Service Instructions Manual page 90

Type b2ha, b2ka, 3.2 to 35 kw gas council no. -system boilers: 41-819-32; 41-819-33; 41-819-34; 41-819-35 -combi boilers: 47-819-28; 47-819-29; 47-819-30
Table of Contents

Advertisement

Code 2
"Solar"/group 4
Coding in the delivered condition
22:8
Start temperature differ-
ential with central heating
backup (code "20:4" must
be selected) 8 K.
23:4
Stop temperature differ-
ential with central heating
backup (code "20:4" must
be selected) 4 K.
24:40
Start temperature for
thermostat function (code
"20:5" or "20:6" must be
selected) 40 °C.
25:50
Stop temperature for
thermostat function (code
"20:5" or "20:6" must be
selected) 50 °C.
26:1
Priority for DHW cylinder
1 with cyclical heating.
(Code "20:9" must be se-
lected).
27:15
Cyclical heating time
15 min.
The DHW cylinder with-
out priority is heated at
most for the duration of
the set cyclical heating
time if the DHW cylinder
with priority is heated up.
28:3
Cyclical pause time
3 min.
90
(cont.)
Possible change
22:2
Start temperature differen-
to
tial adjustable from 2 to
22:30
30 K.
23:2
Stop temperature differen-
to
tial adjustable from 1 to
23:30
29 K.
24:0
Start temperature for ther-
to
mostat function adjustable
24:100
from 0 to 100 K.
25:0
Stop temperature for ther-
to
mostat function adjustable
25:100
from 0 to 100 K.
26:0
Priority for DHW cylinder 1
without cyclical heating.
26:2
Priority for DHW cylinder 2
without cyclical heating.
26:3
Priority for DHW cylinder 2
with cyclical heating.
26:4
Cyclical heating without
priority for either DHW cyl-
inder.
27:5
The cyclical heating time is
to
adjustable from 5 to
27:60
60 min.
28:1
Cyclical pause time is ad-
to
justable from 1 to 60 min.
28:60