Replacing The Control Unit Without The Safety Functions Enabled - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

21.Switch on the inverter power supply again.
22.Perform a reduced acceptance test.
(Page 397)
You have replaced the Control Unit and transferred the safety function settings from the
Operator Panel to the new Control Unit.
8.1.3

Replacing the Control Unit without the safety functions enabled

Replacing a Control Unit with data backup on a memory card
If you use a memory card with firmware, after the replacement, you obtain a precise copy
(firmware and settings) of the replaced Control Unit.
Precondition
You have a memory card with the actual settings of the Control unit to be replaced.
Procedure
To replace the Control Unit, proceed as follows:
1. Disconnect the line voltage to the Power Module and (if installed) the external 24 V
supply or the voltage for the digital outputs of the Control Unit.
2. Remove the signal cables from the Control Unit.
3. Remove the defective Control Unit.
4. Mount the new Control Unit on the Power Module. The new Control Unit must have the
same article number and the same or higher firmware version as the Control Unit that
was replaced.
5. Remove the memory card from the old Control Unit and insert it in the new Control Unit.
6. Reconnect the signal cables of the Control Unit.
7. Connect up the line voltage again.
8. The inverter loads the settings from the memory card.
9. After loading, check whether the inverter outputs alarm A01028.
– Alarm A01028:
– No alarm A01028:
You have successfully replaced the Control Unit.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
Reduced acceptance after component replacement and firmware change
The loaded settings are not compatible with the inverter.
Clear the alarm with p0971 = 1, and recommission the drive.
The inverter accepts the settings that have been loaded.
Corrective maintenance
8.1 Replacing inverter components
383

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents