Correcting An Unsuccessful Firmware Upgrade Or Downgrade - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Corrective maintenance
8.2 Firmware upgrade and downgrade
8.2.3

Correcting an unsuccessful firmware upgrade or downgrade

How does the inverter signal an unsuccessful upgrade or downgrade?
Correcting an unsuccessful upgrade or downgrade
You can check the following to correct an unsuccessful firmware upgrade or downgrade:
● Does the firmware version of your inverter fulfill the preconditions?
– For an upgrade, as a minimum V4.5.
– For a downgrade, as a minimum V4.6.
● Have you correctly inserted the card?
● Does the card contain the correct firmware?
● Repeat the appropriate procedure.
396
The inverter signals an unsuccessful firmware upgrade or down-
grade by a quickly flashing LED RDY and the lit LED BF.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents