Installing The Gsd; Setting The Address - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

4.7.2.4

Installing the GSD

Procedure
To load the GSD of the inverter in the control, proceed as follows:
1. Obtain the GSD
– either on the Internet:
– or from your inverter. To do this, insert a memory card into the inverter and set p0804
2. Unzip the GSDfile in a folder on your computer.
3. Import the GSDinto the configuration tool of your control.
You have now installed the GSD file.
4.7.2.5

Setting the address

Valid address range: 1 ... 125
Procedure
To change the bus address, proceed as follows:
1. Set the address using one of the subsequently listed options:
– using the address switch
– from an operator panel using parameter p0918
– in STARTER using screen form "Control Unit/Communication/PROFIBUS" – or using
2. Switch off the inverter supply voltage.
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
GSD (http://support.automation.siemens.com/WW/view/en/22339653/133100)
= 12. In this way, you will save the GSD on the memory card as (DPGSD.ZIP)
compressed file in the directory /SIEMENS/SINAMICS/DATA/CFG .
Overview of the interfaces (Page 91)
the expert list in parameter p0918
After you have changed the address in STARTER, carry out RAM to ROM (
4.7 Connecting the inverter to the fieldbus
You set the PROFIBUS address of the inverter using
the address switch on the Control Unit, in parameter
p0918 or in STARTER.
In parameter p0918 (factory setting: 126) or in
STARTER, you can only set the address, if all ad-
dress switches are set to "OFF" (0) or "ON" (1).
If you have specified a valid address with the ad-
dress switches, this address will always be the one
that takes effect and parameter p0918 cannot be
changed.
Installing
).
125