Analog Outputs - Siemens SINAMICS G120 Operating Instructions Manual

Low voltage converter with the cu240b-2 and cu240e-2 control units
Hide thumbs Also See for SINAMICS G120:
Table of Contents

Advertisement

Advanced commissioning
6.2 Inverter control
6.2.2.5

Analog outputs

Overview
Not available with Control Units CU240B-2 and
1)
CU240B-2 DP
Defining the analog output type
The inverter offers a series of default settings, which you can select using parameter p0776:
AO 0
AO 1
Characteristics
If you change the analog output type, then the inverter automatically selects the appropriate
scaling of the analog output. The linear scaling characteristic is defined using two points
(p0777, p0778) and (p0779, p0780).
Image 6-5
182
Current output (factory setting)
Voltage output
Current output
Current output (factory setting)
Voltage output
Current output
Examples for scaling characteristics
Changing the function of an analog output:
1. Define the analog output type using
parameter p0776.
2. Interconnect parameter p0771 with a
connector output of your choice.
Interconnecting signals in the
inverter (Page 495)
Connector outputs are marked with
"CO" in the parameter list of the List
Manual.
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
0 mA ... +20 mA
0 V ... +10 V
+4 mA ... +20 mA
Converter with the CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2016, FW V4.7 SP6, A5E34259001B AC
p0776[0] =
0
1
2
p0776[1] =
0
1
2