HART operating data records
B.2 HART job and response data records
HART proto‐
col error dur‐
ing response
5
6
7
8
An external HART request has been rejected because the channel is not the active channel in a
1
redundancy pair. The job must be sent to the connected field device by the partner module
Example of HART programming (HART command interface)
For HART channel 0, command 01 is to be sent in transparent message format to the HART
field device with address "98 CF 38 84 F0".
A positive edge at input 4.0 of a digital input module leads to the writing of the HART command.
The following assumptions are made:
● The module address of the I/O module is 512 (200
● The data record is stored in DB80: starting at address 0.0, length 11 bytes.
● In this example, DB80 (request data record for channel 0) consists of 11 bytes.
m2: CALL SFB53, DB53
84
Meaning
Response error
Query rejected
Profile query rejected
Manufacturer-specific query
rejected
A I 4.0
FP M 101.0
= M 104.0
REQ :=M104.0
ID :=DW#16#200
INDEX :=80
LEN :=11
Explanation
Bit 0 = 1: GAP timeout
Bit 1 = 1: Receive buffer overflow
Bit 2 = 1: Timeout
Bit 3 = 1: Checksum error
Bit 4 = 1: Framing error
Bit 5 = 1: Overflow error
Bit 6 = 1: Parity error
Bit 7 = 1: Reserved
0: Unspecified
1: Compact format not supported
2: SHC not supported
3: Impermissible command
4: No resources
5: Channel in standby mode
6...127: Reserved
128...255: Manufacturer-specific
0: Not specified (not supported)
0: Not specified (not supported)
Explanation
Write request
Module address
Data record number 80
Length 11 bytes
Input/output module AI-DI 16/DQ16x24VDC HART HA (6DL1133-6EW00-0PH1)
1
)
H
Manual, 05/2017, A5E39294170-AA