Bit number
3
4...7
Coding "HART protocol error during response"
HART proto‐
col error dur‐
ing response
0
1
2
3
4
Input/output module AI-DI 16/DQ16x24VDC HART HA (6DL1133-6EW00-0PH1)
Manual, 05/2017, A5E39294170-AA
Meaning
Reserved
HART protocol error during
response
Meaning
Unspecified error
HMD error
Channel fault
Command error
Query error
HART operating data records
B.2 HART job and response data records
Explanation
Always 0
0: Unspecified error
1: HMD error
2: Channel fault
3: Command error
4: Query error
5: Response error
6: Query rejected
7: Profile query rejected
8: Manufacturer-specific query rejected
9 - 15: Not used
Explanation
Always 0
0: Not specified
1: Internal communication error
2: Parameter assignment error
3: HW fault
4: Wait time expired
5: HART timer expired
6...127: Reserved
128...255: Manufacturer-specific
0: Not specified
1: Line fault
2: Short-circuit
3: Open line
4: Low current output
5: Parameter assignment error
6...127: Reserved
128...255: Manufacturer-specific
0-127: HART protocol,
Bit 7 = Always 0
Bit 0 = 0: Reserved
Bit 1 = 1: Receive buffer overflow
Bit 2 = 0: Reserved
Bit 3 = 1: Checksum error
Bit 4 = 1: Framing error
Bit 5 = 1: Overflow error
Bit 6 = 1: Parity error
Bit 7 = 1: Reserved