Siemens SIMATIC ET 200SP Manual page 21

Ha input/output module ai-di 16/dq16x24vdc hart ha
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameter
Measuring range
Diagnostics encoder supply ● Enabled
Diagnostics, Wire break
Diagnostics short-circuit to L
+
Diagnostics overflow
Diagnostics underflow
Diagnostics HART
Wire break limit
Smoothing
Interference frequency sup‐
pression
Number of HART repetitions 0...10
Hardware interrupt high limit
1/2
Hardware interrupt low limit
1/2
Input/output module AI-DI 16/DQ16x24VDC HART HA (6DL1133-6EW00-0PH1)
Manual, 05/2017, A5E39294170-AA
Value range
● 0 to 10 mA
● 0 to 20 mA
● 4 to 20 mA
● 4 to 20 mA HART
There is no underrange in the
ranges 0 to 10 mA or 0 to 20 mA
i.e. the smallest analog value is
zero.
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● Enabled
● Disabled
● 1.185 mA
● 3.6 mA
● None
● Weak
● Medium
● Strong
● 60 Hz (integration time
16.6 ms)
● 50 Hz (integration time 20 ms)
● 10 Hz (integration time
100 ms)
At 50 Hz, the 400 Hz noise is au‐
tomatically also filtered
● Enabled
● Disabled
● Enabled
● Disabled
4.2 Module/channel parameters
Default
Parame‐
ter reas‐
signment
in RUN
4 to 20 mA HART
Yes
Enabled
Yes
Enabled
Yes
Enabled
Yes
Enabled
Yes
Enabled
Yes
Enabled
Yes
1.185 mA
Yes
None
Yes
10 Hz
Yes
5
Yes
Disabled
Yes
Disabled
Yes
Parameters
Efficiency range
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
Channel
21