Structure of HART device status (1st and 2nd status bytes)
Table 6-3
When bit 7 = 1: "Communication error"
Bit 6 = 1
Bit 5 = 1
Bit 4 = 1
Bit 3 = 1
Bit 2 = 0
Bit 1 = 1
Bit 0 = 0
When bit 7 = 0: "No communication error"
When bit 0...6: "Specific in line with response frame"
Table 6-4
Bit 7 = 1
Bit 6 = 1
Bit 5 = 1
Bit 4 = 1
Bit 3 = 1
Bit 2 = 1
Bit 1 = 1
Bit 0 = 1
HART-Fast-Mode
AI-DI 16/DQ16x24VDC HART HA supports the processing of HART commands as SHC
sequence ("Successive HART Command").
If a HART command with set SHC bit is detected, this channel is reserved for external HART
commands for approximately 2 seconds. No internal HART commands are output.
Burst mode
The AI-DI 16/DQ16x24VDC HART HA does not support burst mode. HART commands with
set burst bit are ignored and are not forwarded to the connected field device.
Input/output module AI-DI 16/DQ16x24VDC HART HA (6DL1133-6EW00-0PH1)
Manual, 05/2017, A5E39294170-AA
1st status byte
Parity error
Overflow
Frame error (framing)
Checksum error
Reserved
Overflow in input buffer
Reserved
2nd status byte
Device fault
Configuration changed
Startup (cold start)
Additional status information available
Fixed analog output current setting
Analog output current saturated
Secondary variable outside the limits
Primary variable outside the range
HART function
6.1 How HART works
39