Intelligent Eye Operation - Daikin RMXS-L Series Service Manual

Multi-split type air conditioners
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

CTXG, CTXS, FTXS, CDXS, FDXS, FVXS Series Functions

7.11 INTELLIGENT EYE Operation

Applicable
CTXS07JVJU
CTXS09/12HVJU
Models
CTXS07LVJU
FTXS09/12/15/18/24LVJU
Outline
The microcomputer detects the presence of humans in the room with a motion sensor and reduces
the capacity when there is nobody in the room in order to save electricity.
Details
1. INTELLIGENT EYE detection method
Motion sensor
output
Detection signal
from the motion
sensor
Human detection
signal
2. Motions (in cooling)
Human detection
signal
86
Sampling (20 msec.)
High
Low
(Condition of 10 times or more output)
High
Low
ON
OFF
The motion sensor detects human motion by receiving infrared rays and sends the pulse wave
output.
The microcomputer in the indoor unit carries out a sampling every 20 msec. If the motion sensor
detects 10 times or more of the wave output in one second in total, and the High signal
continues for 3 sec., the microcomputer judges humans are in the room as the human detection
signal is ON.
within
20 min.
ON
OFF
Reset
Target temperature
ON
Remote controller
Sensor button
OFF
ON
Operation
OFF
Fan speed ( )
OFF
In FAN operation, the fan speed is reduced by 60 rpm when no one is in the area.
Human motion
If the detection signal (High) continues for 3 sec. or more,
3 sec.
the microcomputer judges humans are in the room.
20 min.
1 ~ 2˚C (1.8 ~ 3.6 ˚F)
Set speed
60 rpm
1 sec.
If the motion sensor detects the outputs
10 times/sec. or more, the microcomputer
judges the detection signal from the
motion sensor is High.
within
20 min.
Reset
Set speed
Functions and Control
SiUS181631EA
(R24035)
within
20 min.
Reset
(R23920)

Hide quick links:

Advertisement

Table of Contents
loading