Daikin RMXS-L Series Service Manual page 275

Multi-split type air conditioners
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181631EA
7.33.3 Outdoor Fan Motor Connector Check
Check No. 32
(1) Turn the power supply off.
(2) With the fan motor connector disconnected, measure the resistance between each pin, then
Troubleshooting
make sure that the resistance is more than the value mentioned in the following table.
X106A, X107A
(M1F, M2F)
(White) 1
(Orange) 2
(Brown) 3
GND
(Blue) 4
(Unused) 5
(Unused) 6
(Red) 7
Measurement point
1 - 4
2 - 4
3 - 4
4 - 7
(R15634)
Troubleshooting for Outdoor Unit
Judgment
1 MΩ or more
100 kΩ or more
100 Ω or more
100 kΩ or more
265