Field Settings
Detailed Setting Procedure of Low Noise Operation and Demand Control
(1) In setting mode 1, press and hold BS1 (MODE button) for more than 5 seconds. → The system
(2) Press BS2 (SET button) several times and match the LED display with the Setting No. you
(3) Press BS3 (RETURN button) one time, and the present setting content is displayed.
(4) Press BS3 (RETURN button) two times. → The system returns to (1).
(5) Press BS1 (MODE button) one time. → The system returns to setting mode 1 and the H1P goes
(1)
Setting
Setting
Setting No. indication
No.
contents
H1P H2P H3P H4P H5P H6P H7P H1P H2P H3P H4P H5P H6P H7P
12
External low
noise
setting/
setting
22
26
Night-time
low noise
operation
start setting
27
Night-time
low noise
operation
end setting
29
precedence
setting
30
32
Setting mode indication section
136
In setting mode 2, press BS1 (MODE button) one time. → The system enters setting mode 1
and the H1P goes off.
In setting mode 1, the H6P (In low noise operation) and the H7P (In demand control) keep
lighting.
enters setting mode 2 and the H1P lights up.
want.
Press BS2 (SET button) several times and match the LED display with the setting content
(as shown on next page) you want.
off.
(2)
Setting No. indication section
Setting No. indication
contents
NO (Factory
setting)
(Factory
setting)
Level 2
Level 3
PM 8:00
PM 10:00
(Factory
setting)
PM 0:00
AM 6:00
AM 7:00
AM 8:00
(Factory
setting)
Low noise
precedence
(Factory
setting)
60 % of

rated power

consumption
70 % of
(Factory
setting)
80 % of
consumption
OFF
(Factory
setting)
ON
SiUS181631EA
: ON
: OFF
(3)
Setting
Setting contents indication (Initial setting)
H1P H2P H3P H4P H5P H6P H7P
Set contents indication section
Test Operation and Field Settings
l
: Blink
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l
l