Branch Provider (Bp) Unit - Daikin RMXS-L Series Service Manual

Multi-split type air conditioners
Hide thumbs Also See for RMXS-L Series:
Table of Contents

Advertisement

SiUS181631EA
1.2

Branch Provider (BP) Unit

i
Green : Blinks in normal condition
Red : OFF in normal condition
BP Unit LED Indication
Green
A
1
2
j
h
h
j
i
h
j
i
i
j
i
h
i
h
Note:
Turn the power off then on again. If the LED display recurs, the BP unit PCB is defective.
Troubleshooting
h
j
: ON,
: OFF,
: Blinks, —: No matter
Red
3
4
h
h
Normal condition
h
h
Defective electronic expansion valve or anti-icing control in non-operating
indoor unit
h
h
Defective thermistor
i
i
Freeze-up protection control in operating indoor unit or standby indoor unit
Defective BP unit PCB (Refer to note.)
Power supply abnormality (Refer to note.)
Description
LEDA (H1P)
LED1 (H2P)
LED2 (H3P)
LED3 (H4P)
LED4 (H5P)
Troubleshooting with LED
(R19090)