Summary of Contents for Endress+Hauser Gammapilot M FMG60

  • Page 1 Products Solutions Services BA00236F/00/EN/14.14 71253004 Valid for software version: V01.03.06 Operating Instructions Gammapilot M FMG60 Radiometric Measurement AUTHORIZED DISTRIBUTOR: InstrumentsAndControl.com Houston, Texas USA sales@InstrumentsAndControl.com 281-609-7170...
  • Page 2 You can find an overview of all the device functions in the Appendix. A detailed description of all the instrument functions is given in Operating Instructions BA00287F/00/EN "Gammapilot M - Description of Device Functions" which can be found on the CD-ROM supplied. Endress+Hauser...
  • Page 3: Table Of Contents

    Disposal ........71 Contact addresses of Endress+Hauser ..71 Installation .
  • Page 4: Safety Instructions

    Safety instructions Gammapilot M FMG60 HART Safety instructions Designated use The Gammapilot M is a compact transmitter for non-contact level, level limit, density and concentration measurement. The measuring range of a single Gammapilot M extends up to 2 m (6.6 ft). Large measuring ranges of any size can be implemented, however, by cascading several Gammapilot M devices.
  • Page 5: Radiation Protection

    Gammapilot M FMG60 HART Safety instructions Radiation protection The Gammapilot M is used in conjunction with a radioactive source, contained in a source container. When handling radioactive sources, the following instructions have to be observed: 1.4.1 Basic regulations on radiation protection...
  • Page 6: Symbols

    Safety instructions Gammapilot M FMG60 HART Symbols 1.5.1 Safety symbols Symbol Meaning DANGER! DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in serious or fatal injury. A0011189-DE WARNING! WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in serious or fatal injury.
  • Page 7 Gammapilot M FMG60 HART Safety instructions 1.5.4 Symbols for certain types of information Symbol Meaning Allowed Indicates procedures, processes or actions that are allowed. A0011182 Preferred Indicates procedures, processes or actions thar are preferred. A0011183 Forbidden Indicates procedures, processes or actions that are forbidden.
  • Page 8: Identification

    Identification Gammapilot M FMG60 HART Identification Parts of the Gammapilot M Terminal head Mounting collar Detector pipe Measuring range marks Terminal compartment 2 Terminal compartment 1 Supplementary nameplate Centering knob Instrument nameplate 10. Cooling water connections 11. Marking of the radiation...
  • Page 9: Nameplates

    (only for instrument versions with water cooling jacket) Scope of delivery • Ordered version of the device (including Operating Instructions) • Endress+Hauser operating program (on the CD-ROM supplied) • Accessories as ordered Supplied documentation 2.4.1 Operating Instructions (BA00236F/00/EN) Describe how to install and commission the Gammapilot M (communication version 4-20 mA HART).
  • Page 10: Certificates And Approvals

    The device takes into account applicable standards and regulations which are listed in the EC declaration of conformity and thus meets the legal requirements of the EC Directives. Endress+Hauser confirms the successful testing of the instrument by affixing to it the CE mark.
  • Page 11: Installation

    Gammapilot M FMG60 HART Installation Installation Incoming acceptance, transport, storage 3.1.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
  • Page 12: Installation Conditions

    Installation Gammapilot M FMG60 HART Installation conditions 3.2.1 Dimensions, weight Gammapilot M (without water cooling jacket) 537 (22.6) mm (in) A0018072 Gammapilot M with water cooling jacket or collimator 537 (22.6) 12 (0.47) 164 (6.46) mm (in) A0018073 Without water cooling...
  • Page 13 Gammapilot M FMG60 HART Installation 3.2.2 Installation conditions for level measurement Conditions • For level measurements the Gammapilot M is mounted vertically; if possible the detector head should point downwards. • The exit angle of the source container must be exactly aligned to the measuring range of the Gammapilot M.
  • Page 14 Installation Gammapilot M FMG60 HART 3.2.3 Installation conditions for level limit detection Conditions • For level limit detection, the Gammapilot M should be mounted horizontally at the height of the desired level limit. • The exit angle of the source container must be exactly aligned to the measuring range of the Gammapilot M.
  • Page 15 • If only horizontal pipes are accessible, the path of the ray should also be arranged horizontally to reduce the influence of air bubbles and sediments. • The Endress+Hauser clamping device ( ä 72, "Accessories") or an equivalent clamping device should be used for fastening the radiation source container and the Gammapilot M to the measuring tube.The clamping device itself must be installed in a way such that it can...
  • Page 16 Installation Gammapilot M FMG60 HART 3.2.5 Empty pipe detection A0018077 Gammapilot M Monitoring detector FTG20 or FMG60 Mounting the FTG20 or FMG60 on the FMG60 for empty pipe detection If the pipe becomes empty as a result of operational processes, the radiation on the detector side can hit dangerous levels.
  • Page 17: Water Cooling

    Gammapilot M FMG60 HART Installation Water cooling For the versions of the Gammapilot with water cooling jacket, the following applies: • Material: 316L • Water connection: 2 x G 1/4"A, DIN ISO 228 • Inlet temperature: max. 40 °C (104 °F) •...
  • Page 18 Installation Gammapilot M FMG60 HART 3.3.1 Mounting versions A0018079 Recommended mounting position for level measurement: compartment housing at the bottom In exceptional cases (e.g. shortage of space) the compartment housing may be located at the top Mounting position for point level detection and density measurement...
  • Page 19: Installation Check

    Gammapilot M FMG60 HART Installation 3.3.2 Required flow rate The required flow rate depends on • the ambient temperature at the water cooling jacket • the inlet temperature • the measuring range of the Gammapilot M Typical values are given in the following tables: Ambient temperature T = 75 °C (167 °F)
  • Page 20: Wiring

    Wiring Gammapilot M FMG60 HART Wiring Terminal compartments The Gammapilot M has got two terminal compartments: • Terminal compartment 1, for – Power supply – Signal output (depending on the instrument version) • Terminal compartment 2, for – Signal output (depending on the instrument version) –...
  • Page 21: Terminal Assignment

    Gammapilot M FMG60 HART Wiring Terminal assignment Terminal compartment 1 A0018084 90 to 253VAC, 18 to 36 VDC Terminal compartment 2 SIM WP PT100 11 12 IN CASCADE OUT A0018085 Endress+Hauser...
  • Page 22 Wiring Gammapilot M FMG60 HART Terminal(s) Meaning Grounding of the cable screen 1, 2 Power supply Compartment 2: Signal output, depending on communication version: 3, 4 • 4-20mA with HART Compartment 1: • PROFIBUS PA ,(4) • Foundation Fieldbus (Depending on the device version ordered, the signal output is in connection compartment 1...
  • Page 23: Fieldbus Connectors

    Gammapilot M FMG60 HART Wiring Terminal compartment for Feature 30 of the ordering information: Power supply wiring/output wiring Supply voltage Signal output Non-Ex; Non-Ex Ex e; Ex ia Ex e; Ex e Ex d (XP); Ex d (XP) Ex d (XP); Ex ia (IS) Dust-Ex;...
  • Page 24: Potential Equalization

    Wiring Gammapilot M FMG60 HART Potential equalization Before wiring, connect the potential matching line to the external ground terminal of the transmitter. If a water cooling jacket is present, it must be separately connected to the potential matching line. CAUTION In Ex applications, the instrument must only be grounded on the sensor side.
  • Page 25: Wiring In Terminal Compartment 1

    Gammapilot M FMG60 HART Wiring Wiring in terminal compartment 1 CAUTION Before connection please note the following: ‣ When using the instrument in hazardous areas, make sure to comply with national standards and the specifications in the Safety Instructions (XAs). Make sure you use the specified cable gland.
  • Page 26: Wiring In Terminal Compartment 2

    Wiring Gammapilot M FMG60 HART Wiring in terminal compartment 2 CAUTION Before connection please note the following: ‣ Connect potential matching line to transmitter ground terminal and to the ground terminal of the water cooling jacket (if present) before connecting up the instrument ("Potential equalization", ...
  • Page 27: Connecting The

    Gammapilot M FMG60 HART Wiring Connecting the remote display and operation FHX40 The remote display and operating unit FHX40 is available as accessory. It is connected to the FHX40-connector of the Gammapilot M via the supplied cable. To do this, the housing of the Gammapilot M needs not to be opened.
  • Page 28: Wiring In Cascading Mode

    Wiring Gammapilot M FMG60 HART Wiring in cascading mode N/L- L1/L+ AC/DC A0018091 Power supply (90 to 253V or 18 to 36V Junction box Master Slave End-Slave NOTICE For the positioning of the power switch according to IEC/EN 61010, there are two options: ‣...
  • Page 29: Wiring Example For Level Limit Detection 200/400 Mm

    • XA00095R/09/A3: ATEX II (1) G [Ex ia] IIC, ATEX II (1) D [Ex ia] IIIC for RMA42 4.10.2 SIL applications for Gammapilot M FMG60 in conjunction with RMA42 (for point level detection 200/400 mm PVT scintillator) • The Gammapilot M meets SIL2/3 as per IEC 61508, see: –...
  • Page 30: Measuring Solids Flow

    4.11 Measuring solids flow In conjunction with a density measuring device, such as Endress+Hauser' s "Gammapilot M", Promag 55S also determines the rate of solids with regard to the mass, volume or percentage content. The following order information is required for this purpose for Promag 55S: Order option for software function "Solids flow"...
  • Page 31: Operation

    • With a personal computer, Commubox FXA291 with ToF Adapter FXA291 (USB) and the operating program "FieldCare". FieldCare is a graphical operating software for devices from Endress+Hauser. It assists with commissioning, securing data, signal analysis and documentation of the measuring point.
  • Page 32: Display Operation

    Operation Gammapilot M FMG60 HART Display operation 5.2.1 Display and operating elements The LCD module VU331 for displaying and operating is inside the remote display and operating unit FHX40. The measured value can be read off through the FHX40 sight glass.
  • Page 33 Gammapilot M FMG60 HART Operation Function of the keys Key(s) Meaning Navigate upwards in the selection list. Edit numeric value within a function. Navigate downwards in the selection list. Edit numeric value within a function. Navigate to the left within a function group.
  • Page 34 Operation Gammapilot M FMG60 HART 5.2.2 The operating menu Function code The functions of the Gammapilot M are arranged in an operating menu. To ensure easy orientation within the menu, a unique position code is indicated on the display for each function.
  • Page 35 Gammapilot M FMG60 HART Operation Operation using the onsite display VU331 ENDRESS + HAUSER E S C – E S C E S C E S C >3 s Basic setup Todays date Isotop Return to group selection Calibration 3 137 Cs...
  • Page 36: Alternative Operation Options

    FieldCare operating program FieldCare is an Endress+Hauser asset management tool based on FDT technology. With FieldCare, you can configure all Endress+Hauser devices as well as devices from other manufacturers that support the FDT standard. Hardware and software requirements you can find on the internet: www.endress.com...
  • Page 37: Lock/Unlock Configuration

    Gammapilot M FMG60 HART Operation Lock/unlock configuration 5.4.1 Software security locking Enter a number  100 into the "unlock parameter" (*A4) function in the "diagnostics" (*A) function group. The symbol appears on the display. Inputs are no longer possible. If you try to change a parameter, the device jumps to the "unlock parameter" (*A4) function.
  • Page 38: Commissioning

    Commissioning Gammapilot M FMG60 HART Commissioning NOTICE This chapter describes the commissioning of the Gammapilot M using the operating module VU331 (which is located in the remote display and operating unit FHX40). Commissioning using the "FieldCare" or the "Field Xpert SFX100" is similar. For further instructions to the operating program "FieldCare"...
  • Page 39: Switching On The Device

    Gammapilot M FMG60 HART Commissioning Switching on the device NOTICE Error messages A165 "electronics defect" and A635 "present date not defined" The Gammapilot M contains 2 real-time clocks for the decay compensation, which are permanently compared to each other for safety reasons. In order to bridge voltage interruptions, the clocks are buffered with a capacitor.
  • Page 40: Basic Setup

    Commissioning Gammapilot M FMG60 HART Basic setup 6.3.1 "Present date" (*01) On-site display Meaning Present date Date and time of the basic setup are specified in this function. Each of these values must be confirmed by "E" after it has been 17.11.04...
  • Page 41 Gammapilot M FMG60 HART Commissioning 6.3.4 "Operating mode" (*04) On-site display Meaning Operating mode This function is used to specify in which operating mode the Gammapilot M will be used.  Stand alone Master Slave NOTICE The selection can be performed only once and the function is automatically locked after that.
  • Page 42 Commissioning Gammapilot M FMG60 HART 6.3.5 "Measuring mode" (*05) On-site display Meaning Meas. mode This function is used to select the desired measuring mode.  Level Limit Density Further options: • Level measurement (continuous) • Level limit detection • Density measurement (with temperature compensation if required) •...
  • Page 43 Gammapilot M FMG60 HART Commissioning 6.3.6 "Density unit" (*06) On-site display Meaning Density unit This function is needed for density and concentration measure- ments only. It is used to select the density unit.  g/cm3 lb/gal Further options: • g/cm •...
  • Page 44 Commissioning Gammapilot M FMG60 HART 6.3.10 "Pipe diameter" (*0A) On-site display Meaning Pipe diam. This function is needed for density and concentration measure- ments only. It is used to specify the irradiated measuring path 200 mm L. With standard installation, this value is identical to the inner pipe diameter D .
  • Page 45 Gammapilot M FMG60 HART Commissioning 6.3.11 "Output damping" (*0B) On-site display Meaning This function is used to specify the output damping (in Output damping seconds) by which changes of the measured value are attenua- 60 s ted. After a surge in the level or density it takes 5 x until the new measured value is reached.
  • Page 46: Calibration For Level Measurement And Limit Detection

    Commissioning Gammapilot M FMG60 HART Calibration for level measurement and limit detection 6.4.1 Basic principles The calibration points for the measurement are entered in the "calibration" (*1) function group. Each calibration point consists of a level and the associated pulse rate.
  • Page 47 Gammapilot M FMG60 HART Commissioning Empty calibration Refers to the following situation: • The radiation is switched on. • Within the measuring range, the vessel is emptied as far as possible (ideally: 0%, maximum 40%). Calibration points for limit detection...
  • Page 48 That is, not only the level but also the associated pulse rate must be entered by the user. For details concerning the calculation of the count rate please refer to your Endress+Hauser sales organization. NOTICE Calibration date and calibration ‣...
  • Page 49 Gammapilot M FMG60 HART Commissioning 6.4.2 Background calibration Excerpt from the operating menu The following excerpt from the operating menu shows how the background calibration is entered. The individual functions are explained in the sections below. Backgr. calibr. avg. pulse rate bgr.
  • Page 50 Commissioning Gammapilot M FMG60 HART "Avg. pulse rate" (*11) On-site display Meaning Avg. pulse rate The average pulse rate is displayed in this function (after selec- tion of "start" in the previous function). Initially, this value fluc- 186 cps tuates (because of the decay statistics), but due to the integra- tion it reaches an average value in the course of time.
  • Page 51 Gammapilot M FMG60 HART Commissioning 6.4.3 Full and empty calibration or covered and free calibration Excerpt from the operating menu The following excerpt from the operating menu shows how the full and empty calibration (for level measurements) or the covered and free calibration (for level limit detection) are entered.
  • Page 52 Commissioning Gammapilot M FMG60 HART "Value full" (*14) / "Value empty" (*17) On-site display Meaning value full These functions are needed for level measurements only. They are used to specify the level at which the full or empty 100% calibration are performed.
  • Page 53 Gammapilot M FMG60 HART Commissioning "Avg. pulse rate" (*11) On-site display Meaning avg. pulse rate The average pulse rate is displayed in this function (after selection of "start" in the previous function). Initially, this value 2548 cps fluctuates (because of the decay statistics), but due to the integration it reaches an average value in the course of time.
  • Page 54: Additional Settings

    Gammapilot M but in the connected evaluation unit or process transmitter. For further information refer to the Operating Instructions of the respective instrument. If using the Endress+Hauser process transmitter RTA421 or RMA42 the following settings are recommended: For maximum fail-safe mode •...
  • Page 55: Function Group "Safety Settings" (*2)

    Gammapilot M FMG60 HART Commissioning Function group "Safety settings" (*2) On-site display group selection *2Þ  safety settings temp. compensation linearization 6.5.1 "Output on alarm" (*20) On-site display Meaning outp. on alarm This function determines what value the output of the Gamma- pilot M assumes in the event of an alarm condition.
  • Page 56: Sil Locking (For Level Limit Detection 200/400 Mm Pvt Scintillator)

    Commissioning Gammapilot M FMG60 HART SIL locking (for level limit detection 200/400 mm PVT scintillator) SIL locking ("Security locking" (022) function) is in the "Safety settings function group" (S2). It can only be accessed in the "stand alone" operating mode in conjunction with the "level limit"...
  • Page 57 Gammapilot M FMG60 HART Commissioning 6.6.2 Function "security locking" (*22) (SIL unlocking) The FMG60 can be unlocked in SIL2/3 mode by entering the password. If the password is entered correctly, the FMG60 is unlocked. If an incorrect password is entered, the FGM60 goes back to the group selection.
  • Page 58 Commissioning Gammapilot M FMG60 HART 6.6.5 Function "confirm Iout" (*24) (output current during locking) The output current is shifted to <3.6, typically 2.4 mA, by means of the 2nd switch-off path by selecting "Device locked" so the user can clearly see that the FMG60 has actually been locked.
  • Page 59 Gammapilot M FMG60 HART Commissioning 6.6.8 Function "confirm cal." (*27) On-site display Meaning confirm cal. Select "valid" if the data displayed (see _ _ _ _ _ _ ) match the data you entered. Select "not valid" if you want to abort SIL locking.
  • Page 60 Commissioning Gammapilot M FMG60 HART 6.6.12 Function "confirm length" (*2B) On-site display Meaning confirm length Select "valid" if the data displayed (see _ _ _ _ _ _ ) match the data you entered. Select "not valid" if you want to abort SIL locking.
  • Page 61: Calibration For Density And Concentration

    Gammapilot M FMG60 HART Commissioning Calibration for density and concentration measurements 6.7.1 Basic principles The calibration points for the measurement are entered in the "calibration" (*1) function group. Each calibration point consists of a density value and the associated pulse rate.
  • Page 62 Commissioning Gammapilot M FMG60 HART Multiple-point calibration The multiple-point calibration is recommended particularly for measurements in a large density area or for especially exact measurements. Up to 9 calibration points can be used about the whole measuring range. The calibration points should be located as far from each other as possible and should be uniformly distributed over the measuring range.
  • Page 63 Gammapilot M FMG60 HART Commissioning 6.7.2 Background calibration Excerpt from the operating menu The following excerpt from the operating menu shows how the background calibration is entered. The individual functions are explained in the sections below. backgr. calib. avg. pulse rate bgr.
  • Page 64 Commissioning Gammapilot M FMG60 HART "Avg. pulse rate" (*11) On-site display Meaning avg. pulse rate The average pulse rate is displayed in this function (after selec- tion of "start" in the previous function). 186 cps Initially, this value fluctuates (because of the decay statistics), but due to the integration it reaches an average value in the course of time.
  • Page 65 Gammapilot M FMG60 HART Commissioning 6.7.3 Calibration points Excerpt from the operating menu The following excerpt from the operating menu shows, how the density calibration points are entered. The individual functions are explained in the sections below. The functions are only accessible after the background calibration has been performed.
  • Page 66 Commissioning Gammapilot M FMG60 HART "Calibration" (*15) On-site display Meaning calibration This function is used to start the automatic entering of the selected calibration point. stop/edit start Options: • stop/edit This option must be selected if – the calibration point is not to be entered (e.g. because it has already been entered). The pulse rate of the calibration point is then displayed in the following function "density...
  • Page 67 Gammapilot M FMG60 HART Commissioning "Density calibration" (*1B) On-site display Meaning density calibr. The pulse rate of the respective calibration point is displayed in this function. The display value must be confirmed by pressing 1983 cps "E". "-1" indicates, that no pulse rate is present yet. In this case there are two options: •...
  • Page 68 Commissioning Gammapilot M FMG60 HART "Absorption coefficient" (*1E) On-site display Meaning absorp. coeff. This function displays the absorption coefficient which results from the currently active calibration points. The displayed 7.70 mm2/g value should be used for plausibility checking. NOTICE If only one calibration point is currently active, the absorption coefficient is not calculated.
  • Page 69: Density Measurement

    Gammapilot M FMG60 HART Commissioning 6.7.4 Linearization (for concentration measurements) If the concentration is to be measured in a unit other than the "density unit" (*06), a linearization must be performed after the calibration. This can be done in the "Linearization"...
  • Page 70: Maintenance And Repairs

    Repairs to Ex- or SIL-approved devices When carrying out repairs to Ex- or SIL-approved devices, please note the following: • Repairs to Ex- or SIL-approved devices may only be carried out by Endress+Hauser Service in Endress+Hauser workshops. • Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA) and certificates.
  • Page 71: Return

    The measuring device must be returned if repairs of a factory calibration are required, or if the wrong measuring device has been ordered or delivered. According to legal regulations, Endress+Hauser, an ISO-certified company, is required to follow certain procedures when handling returned products that are in contact with medium.
  • Page 72: Accessories

    Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field devices with a CDI interface (Endress+Hauser Common Data Interface) and the USB port of a computer or laptop. For details, see TI00405C/07/EN. For Gammapilot M, you also need the "ToF adapter FXA291" accessory.
  • Page 73: Remote Display Fhx40

    Gammapilot M FMG60 HART Accessories Remote display FHX40 8.5.1 Dimensions 120 (4.72) 88(3.46) 82 (3.23) 118 (4.65) 96 (3.78) max. 80 (3.15) min. 30 (1.18) mm (in) A0018138 Wall-mounting (without mounting bracket) Gammapilot M Cable Pipe-mounting (mounting bracket and plate supplied optionally)
  • Page 74 Accessories Gammapilot M FMG60 HART 8.5.3 Technical data (cable and housing) Max. cable length 20 m (66 ft) (fixed length including the cast-on plugs) Temperature range Temperature class T5: -40 to +75 °C (-40 to +167 °F) Temperature class T6: -40 to +60 °C (-40 to +140 °F) Degree of protection IP65/67 (housing);...
  • Page 75: Mounting Device Fhg60 (For Level Measurement And Level Limit Measurement)

    Gammapilot M FMG60 HART Accessories Mounting device FHG60 (for level measurement and level limit measurement) 8.6.1 Dimensions 88 (3.46) øD M6x80-A2 M6x20-A2 øC max. 6 Nm 116 (4.57) (4.42 lbf ft) 88 (3.46) 63 (2.48) mm (in) A0018139 Spacing as large as possible ...
  • Page 76: Ordering Information

    8.6.3 Ordering information Detailed ordering information is available as follows: • In the Product Configurator on the Endress+Hauser website: www.endress.com ➞ Select country ➞ Instruments ➞ Select device ➞ Accessories for FMG60 • From your Endress+Hauser sales center: www.endress.com/worldwide Product Configurator - the tool for individual product configuration •...
  • Page 77: Clamping Device For Density Measurement Fhg61

    Gammapilot M FMG60 HART Accessories Clamping device for density measurement FHG61 For details, see SD01221F/00/EN. Measurement section for density measurement FHG62 For drawings and description, see SD00540F/00/EN. Endress+Hauser...
  • Page 78: Troubleshooting

    Troubleshooting Gammapilot M FMG60 HART Troubleshooting System error messages 9.1.1 Error signal Errors occurring during commissioning or operation are signaled in the following way: • Error symbol, error code and error description on the display and operating module • Current output, configurable ("output on alarm" (*20) function): –...
  • Page 79: Error Codes

    A110 checksum error Call Endress+Hauser Service A111 electronics defect Switch instrument off/on; If error still is present: call Endress+Hauser service or exchange transmitter A113 electronics defect Switch instrument off/on; If error still is present: call Endress+Hauser service or exchange transmitter...
  • Page 80 Troubleshooting Gammapilot M FMG60 HART Code Description Remedy W642 I_back calibration running Calibration of the current readback path active A631 background not calibrated Perform background calibration ("calibration" (*1) function group) A632 full/covered not calibrated Perform full/covered calibration ("calibration" (*1) function group)
  • Page 81: Possible Calibration Errors

    Gammapilot M FMG60 HART Troubleshooting Possible calibration errors Error Possible cause and remedy Pulse rate too low at • Radiation source switched off  empty vessel Switch on source at the source container • Incorrect alignment of radiation beam ...
  • Page 82: Software History

    Troubleshooting Gammapilot M FMG60 HART Software history Date Software version Software modifications Documentation Since 01.01.02 Original software. BA236F/00/en/08.04 09.2004 52023878 BA287F/00/en/08.04 52023818 Since 01.01.04 Bug fix. 11.2005 Concentration mode corrected. Density measurement recalibration corrected. Since 01.01.06 Bug fix. 08.2006 Corrections for high and low pulse rate.
  • Page 83: Technical Data

    Gammapilot M FMG60 HART Technical Data Technical Data 10.1 Additional technical data For the technical data, please refer to the Technical Information TI00363F/00/EN. 10.2 Documentation This supplementary documentation can be found on our product pages at www.endress.com. • Technical Information (TI00363F/00/EN) •...
  • Page 84 Technical Data Gammapilot M FMG60 HART Certificates Allocation to the option, see the Product Configurator on the Endress+Hauser website: www.endress.com ➞ Select country ➞ Instruments ➞ Select device ➞ Product page function: Configure this product General Approval Type of protection...
  • Page 85 Gammapilot M FMG60 HART Technical Data Approval number: KEMA 04 ATEX 1153 Approval Type of protection Power supply wiring/ Output Approval Feature 010 Output wiring (Communication) number Option 030 Option 040 XA00303F 2, 3 XA00332F II 2(1) G Ex de [ia Ga] IIC T6 Gb...
  • Page 86 Option 040 TIIS Ex d [ia] IIC T6 BA00236F CE mark The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the device passing the required tests by attaching the CE-mark. GOST Approval for GOST available. Overfill protection WHG for level limit detection.
  • Page 87 Gammapilot M FMG60 HART Technical Data Endress+Hauser...
  • Page 88: Appendix

    Appendix Gammapilot M FMG60 HART Appendix 11.1 Operating menu for level measurements beam type isotope operating mode basic setup todays date standard / cont. 137Cs slave dd.mm.yy hh:mm modulated 60 Co end slave no compens. not defined stand alone meas. mode...
  • Page 89 Gammapilot M FMG60 HART Appendix output damping 1 … 999 s Default: 6 s calibration avg. pulse rate full calibr start -1: not calibrated stop/edit next point calibration avg. pulse rate empty calibr start -1: not calibrated stop/edit next point calibration avg.
  • Page 90: Operating Menu For Level Limit Detection

    Appendix Gammapilot M FMG60 HART 11.2 Operating menu for level limit detection basic setup todays date beam type isotope operating mode dd.mm.yy hh:mm standard / cont. 137Cs slave modulated 60 Co end slave no compens. not defined stand alone meas. mode...
  • Page 91 Gammapilot M FMG60 HART Appendix output damping 1 … 999 s Default: 6 s calibration avg. pulse rate full calibr start -1: not calibrated stop/edit next point calibration avg. pulse rate empty calibr start -1: not calibrated stop/edit stop/edit conf. backgr conf.
  • Page 92: Operating Menu For Density And Concentration

    Appendix Gammapilot M FMG60 HART 11.3 Operating menu for density and concentration measurements operating mode basic setup todays date beam type isotope slave dd.mm.yy hh:mm standard / cont. 137Cs end slave modulated 60 Co not defined no compens. stand alone meas.
  • Page 93 Gammapilot M FMG60 HART Appendix density unit min. density max. density pipe diam. unit pipe diam. outp. damp. g/cm3 1 … 999 s Default: 60 s … next point density calibr density value calibr . point absorp. coef ref. pulse rate without temp.
  • Page 94: Index

    Gammapilot M FMG60 HART Index Symbols *01 - Present date ....... 40 Cable entries .
  • Page 95 Gammapilot M FMG60 HART Manual calibration ......48, 62 Measurement section ......77, 83 Measuring range marks .