Operating Instructions

Levelflex M FMP41C
Guided Level-Radar
HART/4...20 mA
6
BA276F/00/en/11.06
No. 52021033
Valid as of software version
V 01.04.00 (amplifier)
V 01.04.00 (communication)

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Levelflex M FMP41C

  • Page 1: Operating Instructions

    Operating Instructions Levelflex M FMP41C Guided Level-Radar HART/4...20 mA BA276F/00/en/11.06 No. 52021033 Valid as of software version V 01.04.00 (amplifier) V 01.04.00 (communication)
  • Page 2 Brief overview Levelflex M FMP41C with HART/4...20 mA Brief overview For quick and simple commissioning: → ä 6 Safety Instructions Explanation of the warning symbols You can find special instructions at the appropriate position in the chapter in question. The positions are indicated with the icons Warning #, Caution " and Note !.
  • Page 3 Levelflex M FMP41C with HART/4...20 mA Brief overview Brief operating instructions KA 189F/00/a2/11.05 Levelflex M - Brief operating instructions 52012501 Contrast: measured value dist./ meas value Group selection process empty check start basic setup tank medium full dist./ range of...
  • Page 4 Brief overview Levelflex M FMP41C with HART/4...20 mA Endress + Hauser...
  • Page 5: Table Of Contents

    Operational safety ......6 Contact addresses of Endress+Hauser ... 76 Notes on safety conventions and icons .
  • Page 6: Safety Instructions

    Levelflex M FMP41C with HART/4...20 mA Safety instructions Designated use The Levelflex M FMP41C is a compact level transmitter for the continuous measurement of solids and liquids, measuring prinziple: Guided Level Radar / TDR: Time Domain Reflectometry. Installation, commissioning and operation The Levelflex M has been designed to operate safely in accordance with current technical, safety and EU standards.
  • Page 7: Notes On Safety Conventions And Icons

    Levelflex M FMP41C with HART/4...20 mA Safety instructions Notes on safety conventions and icons In order to highlight safety-relevant or alternative operating procedures in the manual, the following conventions have been used, each indicated by a corresponding symbol in the margin.
  • Page 8: Identification

    Dat./Insp.: D01301-A Reference to additional safety-relevant documentation L00-FMP4xxxx-18-00-00-en-001 Fig. 1: Information on the nameplate of the Levelflex M FMP41C (example) 2.1.2 Ordering structure This overview does not mark options which are mutually exclusive. Ordering structure Levelflex M FMP41C Approval: A Non-hazardous area...
  • Page 9 Levelflex M FMP41C with HART/4...20 mA Identification Ordering structure Levelflex M FMP41C (continued) Probe: A ..mm, rope PFA>316, 150mm, Center rod, nozzle height max 150mm ..mm, rope PFA>316, 300mm, Center rod, nozzle height max 300mm C ..mm, rope PFA>316, 450mm, Center rod, nozzle height max 450mm D ..
  • Page 10 Identification Levelflex M FMP41C with HART/4...20 mA Ordering structure Levelflex M FMP41C (continued) Power Supply; Output: 2-wire; 4…20mA HART D 2-wire; PROFIBUS PA 2-wire; FOUNDATION Fieldbus G 4-wire 90...250VAC; 4...20mA HART H 4-wire 10.5...32VDC; 4...20mA HART Special version Operation: W/o display, via communication...
  • Page 11: Scope Of Delivery

    The device complies with the applicable standards and regulations as listed in the EC declaration of conformity and thus complies with the statutory requirements of the EG directives. Endress+Hauser confirms the successful testing of the device by affixing to it the CE mark.
  • Page 12: Installation

    Installation Levelflex M FMP41C with HART/4...20 mA Installation Incoming acceptance, transport, storage 3.1.1 Incoming acceptance Check the packing and contents for any signs of damage. Check the shipment, make sure nothing is missing and that the scope of supply matches your order.
  • Page 13: Installation Conditions

    Levelflex M FMP41C with HART/4...20 mA Installation Installation conditions 3.2.1 Dimensions Housing dimensions Dimensions for the process connection and the probe type → ä 14. max. 110 ENDRESS+HAUSER F12 housing (Aluminium) L00-F12xxxx-06-00-00-en-001 max. 100 ENDRESS+HAUSER T12 housing (Aluminium) L00-T12xxxx-06-00-00-en-001 max. 94...
  • Page 14 Installation Levelflex M FMP41C with HART/4...20 mA Levelflex M FMP41C - process connection, probe type Housing dimensions → ä 13 F12 / T12 / F23 housing Variant “3”: remote electronic 4 x Ø 8,5 Variant “4”: remote electronic Ø 21.3 with angled adaptor Ø...
  • Page 15: Installation

    Levelflex M FMP41C with HART/4...20 mA Installation Installation 3.3.1 Mounting kit In addition to the tool needed for flange mounting, you will require the following tool: • 4 mm Allen wrench for turning the housing. 3.3.2 Mounting probes " Caution! If there is a risk of electrostatic discharge from the product, then both processconnection and rope must be earthed before the probe is lowered into the silo.
  • Page 16: General Instructions

    Installation Levelflex M FMP41C with HART/4...20 mA 3.3.3 General instructions Normally use rod or coax probes for liquids. Rope probes are used in liquids for measuring ranges > 4m and with restricted ceiling clearance which does not allow the installation of rigid probes.
  • Page 17 Levelflex M FMP41C with HART/4...20 mA Installation Type of probe mounting • When installing in plastic tanks, the nozzle must have at least DN50/2". The appropriate flange must be used as the process connection. • For nozzles up to 450 mm high, select the length of the centering rod appropriate for the nozzle height when using rope probes.
  • Page 18 Installation Levelflex M FMP41C with HART/4...20 mA 3.3.4 Special instructions When installing in stirring tanks, observe lateral load of probes. Possibly check whether a non- contact process, ultrasound or radar would not be better suited, above all if the stirrer generates large mechanical loads on the probe.
  • Page 19 Levelflex M FMP41C with HART/4...20 mA Installation 3.3.5 Notes on special installation situations Installation at an angle • For mechanical reasons, the probe should be installed as vertically as possible. • Installation with a deviation up to approx. 5° from the vertical axis is permitted for probes up to approx.
  • Page 20 Installation Levelflex M FMP41C with HART/4...20 mA 3.3.6 Installation for difficult to access process connections Installation with remote electronic • Follow installation instructions on → ä 16 • Mount housing on a wall or pipe as shown in the diagram.
  • Page 21: Turn Housing

    Levelflex M FMP41C with HART/4...20 mA Installation Turn housing After mounting, the housing can be turned 350° in order to simplify access to the display and the terminal compartment. Proceed as follows to turn the housing to the required position: •...
  • Page 22: Wiring

    Wiring Levelflex M FMP41C with HART/4...20 mA Wiring Quick wiring guide Wiring in F12/F23 housing " Before connection please note the following: The power supply must be identical to the data on the Caution! nameplate (1). ENDRESS+HAUSER Made in Germany...
  • Page 23 Levelflex M FMP41C with HART/4...20 mA Wiring Wiring in T12 housing " Before connection please note the following: The power supply must be identical to the data on the nameplate (1). Caution! ENDRESS+HAUSER Made in Germany LEVELFLEX-M D-79689 Maulburg Switch off power supply before connecting up the device.
  • Page 24: Connecting The Measuring Unit

    Wiring Levelflex M FMP41C with HART/4...20 mA Connecting the measuring unit Terminal compartment Three housings are available: • Aluminium housing F12 with additionally sealed terminal compartment for: – standard, – EEx ia. • Aluminium housing T12 with separate terminal compartment for: –...
  • Page 25 Levelflex M FMP41C with HART/4...20 mA Wiring Cable entry Cable gland: M20x1.5 Cable entry: G ½ or ½ NPT Supply voltage HART, 2-wire The following values are the voltages across the terminals directly at the instrument: Terminal voltage Current Communication...
  • Page 26 Wiring Levelflex M FMP41C with HART/4...20 mA Overvoltage protection If the measuring device is used for the level measurement in flammable liquids which requires the use of an overvoltage protection according to DIN EN 60079-14, standard for testprocedures DIN IEC 60060-1 (10 kA, Puls 8/20 µs) it has to be ensured that •...
  • Page 27: Recommended Connection

    Levelflex M FMP41C with HART/4...20 mA Wiring " Caution! If the HART communication resistor is not built into the supply unit and the HART interface is to be used, it is necessary to insert a communication resistor of 250 Ω into the 2-wire line.
  • Page 28: Operation

    Operation Levelflex M FMP41C with HART/4...20 mA Operation Quick operation guide ENDRESS + HAUSER – >3 s Return to basic setup tank shape medium property Group Selection Standard safety settings aluminium tank plastic tank linearisation bypass / pipe extended calibr.
  • Page 29 Levelflex M FMP41C with HART/4...20 mA Operation 5.1.1 General structure of the operating menu The operating menu is made up of two levels: • Function groups (00, 01, 03, …, 0C, 0D): The individual operating options of the instrument are split up roughly into different function groups.
  • Page 30: Display And Operating Elements

    Operation Levelflex M FMP41C with HART/4...20 mA Display and operating elements Four lines with 20 characters each. Display contrast adjustable through key combination. (liquid crystal display) Orde Orde r Cod r Cod Ser.- Ser.- No.: No.: sber sber surin surin...
  • Page 31 Levelflex M FMP41C with HART/4...20 mA Operation 5.2.2 Display symbols The following table describes the symbols that appear on the liquid crystal display: Sybmol Meaning ALARM_SYMBOL This alarm symbol appears when the instrument is in an alarm state. If the symbol flashes, this indicates a warning.
  • Page 32: Local Operation

    Operation Levelflex M FMP41C with HART/4...20 mA Local operation 5.3.1 Locking of the configuration mode The Levelflex can be protected in two ways against unauthorised changing of instrument data, numerical values or factory settings: "unlock parameter" (0A4): A value <> 100 (e.g. 99) must be entered in "unlock parameter" (0A4) in the "diagnostics"...
  • Page 33 There is no need to change these parameters under normal circumstances and consequently, they are protected by a special code known only to the Endress+Hauser service organization. Please contact Endress+Hauser if you have any questions.
  • Page 34 Operation Levelflex M FMP41C with HART/4...20 mA 5.3.3 Factory settings (Reset) " Caution! A reset sets the instrument back to the factory settings. This can lead to an impairment of the measurement. Generally, you should perform a basic setup again following a reset.
  • Page 35: Display And Acknowledging Error Messages

    Levelflex M FMP41C with HART/4...20 mA Operation Display and acknowledging error messages Type of error Errors that occur during commissioning or measuring are displayed immediately on the local display. If two or more system or process errors occur, the error with the highest priority is the one shown on the display.
  • Page 36: Hart Communication

    5.5.2 ToF Tool operating program The ToF Tool is a graphical operation software for instruments from Endress+Hauser. It is used to support commissioning, securing of data, signal analysis and documentation of the instruments. It is compatible with the following operating systems: WinNT4.0, Win2000 and WinXP.
  • Page 37 Levelflex M FMP41C with HART/4...20 mA Operation Menu-guided commissioning L00-FMP4xxxx-20-00-00-de-002 Signal analysis via envelope curve: L00-FMP4xxxx-20-00-00-de-007 Connection options • HART mit Commubox FXA191/FXA195 • Service-interface with adapter FXA193 (RS232C) or FXA291 and ToF Adapter FXA291 (USB) Endress + Hauser...
  • Page 38: Commissioning

    Commissioning Levelflex M FMP41C with HART/4...20 mA Commissioning Function check Make sure that all final checks have been completed before you start up your measuring point: • Checklist “Post-installation check” (→ ä 21). • Checklist “Post-connection check” (→ ä 21).
  • Page 39: Basic Setup

    Levelflex M FMP41C with HART/4...20 mA Commissioning Basic Setup tank shape flange: Standard reference point of measurement measuring cond. Unknown measuring cond. Standard empty calibr. full calibr. mapping E = empty calibr. (= zero) LN = probe length setting in 005...
  • Page 40 Commissioning Levelflex M FMP41C with HART/4...20 mA The basic setup is sufficient for successful commissioning in most applications. The Levelflex is initially adjusted at the factory to the probe length ordered, so that in most cases only the application parameters, that automatically adapt the device to the measuring conditions, need to be entered.
  • Page 41: Basic Setup With The Vu331

    Levelflex M FMP41C with HART/4...20 mA Commissioning Basic Setup with the VU331 Function "measured value" (000) ⇒ ENDRESS + HAUSER – This function displays the current measured value in the selected unit (see "customer unit" (042)) function). The number of digits after decimal point can be selected in the "no.of decimals"...
  • Page 42 Commissioning Levelflex M FMP41C with HART/4...20 mA bypass / pipe The "bypass / pipe" option is designed especially for the installation of probes in a bypass or a stilling well. If this option is selected, the upper blocking distance is preset to 100 mm.
  • Page 43 Levelflex M FMP41C with HART/4...20 mA Commissioning Function "process propert." (004) ⇒ ENDRESS + HAUSER – Use this function to adapt the device reaction to the filling speed in the tank. The setting impacts on an intelligent filter. Selection: • standard •...
  • Page 44 Commissioning Levelflex M FMP41C with HART/4...20 mA Function "probe length" (031) ⇒ ENDRESS + HAUSER – Use this function to select whether the probe length was changed after factory calibration. Only then is it necessary to enter or correct the probe length.
  • Page 45 Levelflex M FMP41C with HART/4...20 mA Commissioning After selection "length too short" or "length too long", the calculation of the new value need approx. 10 s. Function "empty calibr." (005) ⇒ ENDRESS + HAUSER – This function is used to enter the distance from the flange (reference point of the measurement) to the minimum level (=zero).
  • Page 46 Commissioning Levelflex M FMP41C with HART/4...20 mA 100% F = full calibration (= span) F max = E – upper blocking distance L00-FMP4xxxx-14-00-06-en-009 Note! The usable measuring range lies between the lower and the upper blocking distance. The values for empty distance (E) and span (F) can be set independently of this.
  • Page 47 Levelflex M FMP41C with HART/4...20 mA Commissioning distance too small distance = ok L00-FMP4xxxx-14-00-06-en-010 distance = ok Use this function at part-covered probe. Choosing function "manual" or "probe free" at free probe. • mapping is carried out up to the currently measured echo •...
  • Page 48 Commissioning Levelflex M FMP41C with HART/4...20 mA Function "range of mapping" (052) ⇒ ENDRESS + HAUSER – This function displays the suggested range of mapping. The reference point is always the reference point of the measurement (→ ä 39). This value can be edited by the operator.
  • Page 49: Blocking Distance

    Levelflex M FMP41C with HART/4...20 mA Commissioning Blocking distance Function "upper block. dist" (059) ⇒ ENDRESS + HAUSER – For rod probes and for rope probes with lengths of up to 8 m, the upper blocking distance is preset to 0.2 m on delivery.
  • Page 50 Commissioning Levelflex M FMP41C with HART/4...20 mA Maximum measured error Typical statements for reference conditions: DIN EN 61298-2, percentage of the span. Output: digital analogue sum of non-linearity, measurig range: ± 0.06 % non-repeatability – up to 10 m: ±5 mm and hysteresis –...
  • Page 51: Envelope Curve With Vu331

    Levelflex M FMP41C with HART/4...20 mA Commissioning Envelope curve with VU331 After the basic setup, an evaluation of the measurement with the aid of the envelope curve ("envelope curve" (0E)) function group) is recommended.). 6.6.1 Function "plot settings" (0E1) ⇒...
  • Page 52: Function "Envelope Curve Display" (0E3)

    Commissioning Levelflex M FMP41C with HART/4...20 mA Function "envelope curve display" (0E3) You can obtain the following information from the envelope curve display in this function: quality of evaluated echo full calibr. evaluated echo empty calibr. is marked envelope curve...
  • Page 53 Levelflex M FMP41C with HART/4...20 mA Commissioning Horizontal-Zoom-Modus Press , to switch to the envelope curve navigation. You are then in Horizontal Zoom mode. Either is displayed. You now have the following options: • increases the horizontal scale. • decreases the horizontal scale.
  • Page 54: Basic Setup With The Tof Tool

    Commissioning Levelflex M FMP41C with HART/4...20 mA Exiting the navigation • Press again to run through the different modes of the envelope curve navigation. • Press to exit the navigation. The set increases and shifts are retained. Only when you reactivate the "recording curve"(0E2) function does the Levelflex use the standard display...
  • Page 55 Levelflex M FMP41C with HART/4...20 mA Commissioning Basic Setup step 2/6: • Enter the application parameters: – tank properties (for a description, → ä 41) – medium properties (for a description, → ä 42) – process properties (for a description, → ä 43)
  • Page 56 Commissioning Levelflex M FMP41C with HART/4...20 mA Basic Setup step 4/6: • Enter the application parameters: – probe length (for a description, → ä 44) – probe (for a description, → ä 44) – probe length (for a description, → ä 44) –...
  • Page 57 Levelflex M FMP41C with HART/4...20 mA Commissioning Basic Setup step 6/6: • This step starts the tank mapping • The measured distance and the current measured value are always displayed in the header • for a description, → ä 48) l00-fmp4xxxx-20-00-00-en-004 6.8.1...
  • Page 58 Commissioning Levelflex M FMP41C with HART/4...20 mA 6.8.2 Envelope curve with the ToF Tool After the basic setup, an evaluation of the measurement using the envelope curve is recommended (→ ä 58). L00-FMP4xxxx-20-00-00-en-007 Note! For the optimization of the measurement the installation of the Levelflex in another place can be executed when enterference echoes.
  • Page 59 Levelflex M FMP41C with HART/4...20 mA Commissioning Evaluation of the measurement: • The map must correspond to the course of the envelope curve (for rod probes up to approx. 5 cm and for rope probes up to approx. 25 cm before the end of the probe) when the tank is empty.
  • Page 60: Maintenance

    They contain the related replacement instructions. All the spare parts kits which you can order from Endress+Hauser for repairs to the Levelflex M are listed with their order numbers on → ä 70 and 73. Please contact Endress+Hauser Service for further information on service and spare parts.
  • Page 61: Accessories

    Levelflex M FMP41C with HART/4...20 mA Accessories Accessories Various accessories, which can be ordered separately from Endress+Hauser, are available for the Levelflex M. Weather protection cover A Weather protection cover made of stainless steel is recommended for outdoor mounting (order code: 543199-0001).
  • Page 62 TI404F/00/en. Commubox FXA291 The Commubox FXA291 connects Endress+Hauser field instruments with CDI interface (= Endress+Hauser Common Data Interface) to the USB interface of a personal computer or a notebook. For details refer to TI405C/07/en. Note! For the following Endress+Hauser instruments you need the "ToF Adapter FXA291" as an additional accessory: •...
  • Page 63 Levelflex M FMP41C with HART/4...20 mA Accessories Remote display FHX40 Wall-mounting Pipe-mounting (without mounting bracket) (mounting bracket and plate supplied optionally, s. product structure) Separate housing FHX 40 (IP 65) Micropilot M Levelflex M Prosonic M O rd O rd...
  • Page 64 Accessories Levelflex M FMP41C with HART/4...20 mA Isolated tie down Mounting-kit Order - No. Reliable, isolated mounting for 4mm rope probe 52014249 for 6mm rope probe 52014250 If a rope probe has to be fixed and asecure grounded mounting is not possible, we recommend using the insulating...
  • Page 65: Trouble-Shooting

    Levelflex M FMP41C with HART/4...20 mA Trouble-shooting Trouble-shooting Trouble-shooting instructions Levelflex M -Trouble Shooting Check voltage and Not ok compare it with the Instrument does Connect the Instrument works? Ready specifications on the not respond correct voltage nameplate. Check the polarity...
  • Page 66: System Error Messages

    Trouble-shooting Levelflex M FMP41C with HART/4...20 mA System error messages Code Description Possible cause Remedy A102 checksum error device has been powered off before data reset general reset & new calibr. could be stored; avoid emc problem; required emc problem;...
  • Page 67 Levelflex M FMP41C with HART/4...20 mA Trouble-shooting Code Description Possible cause Remedy W601 linearisation ch1 curve not linearization not monotonously increasing correct linearisation table monotone W611 less than 2 linearisation number of entered linearization points < 2 correct linearisation table...
  • Page 68: Application Errors

    Trouble-shooting Levelflex M FMP41C with HART/4...20 mA Application errors Error Output Possible cause Remedy A warning or alarm Depending on the configuration See table of 1. See table of error messages (→ ä 66) has occurred. error messages (→ ä 66) →...
  • Page 69 Levelflex M FMP41C with HART/4...20 mA Trouble-shooting Device displays a Incorrect probe length 1. Carry out automatic probe length level when the detection when the tank is tank is empty. empty. 20 mA/100% 2. Carry out mapping over entire probe when the tank is empty (probe free!).
  • Page 70: Spare Parts

    Spare parts Note! You can order spare parts directly from your Endress+Hauser service organization by giving the serial number which is printed on the measuring transducer nameplate (→ ä 8). The corresponding spare part number also appears on each spare part. Installation instructions are given on the instruction card that is also delivered.
  • Page 71 Levelflex M FMP41C with HART/4...20 mA Trouble-shooting 10 Housing 52013409 Housing F12, aluminium, coated, M20, metal 52013348 Housing F12, aluminium, coated, G1/2, 4-wire 52013349 Housing F12, aluminium, coated, NPT1/2, 4-wire 52013350 Housing F12, aluminium, coated, M20, 4-wire 52013351 Housing F12, aluminium, coated, M20, metal...
  • Page 72 Trouble-shooting Levelflex M FMP41C with HART/4...20 mA Spare parts for Levelflex M FMP41C housing type F23 20 Cover 52018670 Cover F23 316L, sight glass, gasket 52018681 Cover F23 316L, gasket Endress + Hauser...
  • Page 73 Levelflex M FMP41C with HART/4...20 mA Trouble-shooting Spare parts for Levelflex M FMP41C housing type T12 with separate connecting compartment O rd r. -N d e : I L O o .: s s b e re a s u...
  • Page 74 Trouble-shooting Levelflex M FMP41C with HART/4...20 mA 10 Housing 52006205 Housing T12, aluminium, M20, PEL, cover 543180-1023 Housing T12, aluminium, NPT1/2, PEL 11 Hood for terminal compartment 52005643 Hood T12 12 Set of screws 535720-9020 Set of screws for housing F12/T12...
  • Page 75 Levelflex M FMP41C with HART/4...20 mA Trouble-shooting FMP41C - probes, accessories and spare parts In preparation. Endress + Hauser...
  • Page 76: Return

    Levelflex M FMP41C with HART/4...20 mA Return The following procedures must be carried out before a transmitter is sent to Endress+Hauser e.g. for repair or calibration: • Remove all residue which may be present. Pay special attention to the gasket grooves and crevices where fluid may be present.
  • Page 77: Technical Data

    Levelflex M FMP41C with HART/4...20 mA Technical data Technical data 10.1 Additional technical data 10.1.1 Input The measured variable is the distance between a reference point (see Fig. on → ä 14) and the Measured variable product surface. Subject to the input empty distance (E, see Fig. on → ä 86), the level is calculated.
  • Page 78 Technical data Levelflex M FMP41C with HART/4...20 mA Influence of ambiente The measurements are carried out in accordance with EN 61298-3: temperature • digital output: – FMP41C average T : 0.6 mm/10 K, max. ±3.5 mm over the entire temperature range -40 °C...+80 °C 2-wire: •...
  • Page 79 +200° C [392 °F] measured here For FMP41C with Endress+Hauser adapter 43 mm: 0 °C ... 150 °C (32 °F...302 °F). Lateral load-bearing capacity of the rod probe: 30 Nm Process pressure limits All models: Vacuum up to max. 40 bar (585,9psi).
  • Page 80 Technical data Levelflex M FMP41C with HART/4...20 mA ε r ≥ 1.6 Dielectric constant • Rod and rope probe: 10.1.6 Mechanical construction Tolerance of probe length Rod probes over 1 m / 3.2 ft 3 m / 9.8 ft 6 m / 20 ft up to 1 m / 3.2 ft...
  • Page 81 10.1.7 Certificates and approvals CE approval The measuring system meets the legal requirements of the EC-guidelines. Endress+Hauser confirms the instrument passing the required tests by attaching the CE-mark. Ex approval Correlation of safety instructions (XA) and certificates (ZE) to the instrument:...
  • Page 82 Technical data Levelflex M FMP41C with HART/4...20 mA External standards and EN 60529 guidelines Protection class of housing (IP-code) EN 61010 Safety regulations for electrical devices for measurement, control, regulation and laboratory use. EN 61326 Emissions (equipment class B), compatibility (appendix A - industrial area) NAMUR NE 21 Electromagnetic Compatibility (EMC) of Industrial Process and Laboratory Control Equipment.
  • Page 83 Levelflex M FMP41C with HART/4...20 mA Technical data Endress + Hauser...
  • Page 84: Appendix

    Appendix Levelflex M FMP41C with HART/4...20 mA Appendix 11.1 Operating menu HART (Display modul), ToF Tool basic setup tank properties medium cond. process proper. determine length empty calibr. end of probe 030 see Function group “leghth adjustment 03” enter value...
  • Page 85 Levelflex M FMP41C with HART/4...20 mA Appendix full calibr. dist./meas.value check distance range of mapping start mapping dist./meas.value enter value distance = ok input of D and L dist. too small mapping range are displayed D and L manual are displayed probe free dist.
  • Page 86: Description Of Functions

    Appendix Levelflex M FMP41C with HART/4...20 mA 11.2 Description of functions Note! A detailed description of the function groups, functions and parameters is given in the documentation BA245F – "Description of the instrument functions" on the enclosed CD-ROM. 11.3 Function and system design 11.3.1...
  • Page 87 • with a Personal Computer, FXA193 (RS232C) or FXA291 and ToF Adapter FXA291 (USB) and the operating software "ToF Tool - FieldTool Package" respectively "FieldCare". The ToF Tool is a graphical operating software for instruments from Endress+Hauser that operate based on the time-of-flight principle (radar, ultrasonic, guided micro-impulse). It assists with commissioning, securing data, signal analysis and documentation of the measuring point.
  • Page 88 Appendix Levelflex M FMP41C with HART/4...20 mA Endress + Hauser...
  • Page 89: Index

    Levelflex M FMP41C with HART/4...20 mA Index Index Accessories ........61 Maintenance .